H0361900.E - EN - 2015-02
7
• Switch on the filter system.
• Progressively close valve 1 in order to increase the filter pressure to 150 g (0.150 bar).
• Open valves 2, 3 and 4 completely, then half open valve 5 (see §2.3) (the air accumulated in the heat pump condenser
and in the filter circuit is then bled).
If valves 4 and 5 are not fitted, open valve 1 completely, and half close valve 3.
• Power-up the heat pump,
• If the heat pump is on stand-by:
, press on
for 3 seconds,
will appear for 2
seconds, and
(different soft number according to model) for 3 seconds, and the water and set-point
temperatures will be displayed:
, a 2-minute delay will start.
• Set the required water temperature:
- press
to increase temperature,
- press
to decrease temperature,
When the pool reaches the required temperature, the heat pump will automatically stop.
• Set the water flow-rate using the menu , when the indicator
is steady: press
to display the water flow-rate
status:
Status
Water flow-rate ok
No water flow
Water flow-rate too weak
Water flow-rate too strong
Display
• Set the flow-rate using valve 5 (or 3 if no valve 5 is fitted), and, to quit the menu, press
.
During this adjustment phase, wait for a few minutes after each change in valve position to allow the device
to balance.
3.3 Checks to perform after start-up
The heat pump must stop when:
• The set-point temperature is lowered using the digital control panel,
• Filtering is stopped or valve 2 or 3 is closed 3,
• Turn off the regulator by pressing and holding the
button for 3 seconds.
3.4 Wintering
Wintering is imperative, failure to do so exposes the condenser to a risk of freezing, this situation is not
covered by the warranty. To avoid condensation damaging the appliance, do not cover it hermetically.
• Switch the digital control panel to «stand-by» mode by pressing
for 3 seconds, and cut the power supply,
• Open valve 1,
• Close valves 2 and 3, and open valves 4 and 5 (if fitted),
• Ensure that no water is flowing through the heat pump,
• Drain the water condenser by unscrewing the two pool water inlet and outlet connections at the back of the heat pump,
• In the case of full winter storage conditions for the pool: re-connect the inlet and outlet connections to avoid foreign
bodies entering into the condenser,
• In the case of winter storage for the heat pump alone: do not reconnect the inlet and outlet connectors, instead place
two plugs (supplied) on the condenser water inlet and outlet.
4. Maintenance
4.1 Maintenance instructions
It is recommended to carry out general servicing of the appliance on wintering and recommissioning (at least
once per year), in order to check it is in good working order and maintain its performances, as well as to
prevent certain possible defects. These actions are the user’s responsibility and must be carried out by a
technician.
Do not use high pressure cleaners.
• Ensure no foreign bodies obstruct the fan grid.
• Clean the evaporator with a soft brush and a fresh water jet (disconnect the power cable), do not twist or bend the
metal blades, then to clean the discharge pipe of the condensates in order to evacuate the impurities which could block
it.