Clearances
Minimum vertical clearance = 36 inches
Minimum clearance to at least one door panel = 18 inches
Water Flow
Water Inlet
Water Outlet
Combustion and Ventilation requirements.
Appropriate site location
Clearances/ Combustable sufaces
In both indoor installations (US) and outdoor shelter
installations (Canada), the heater must be placed to
provide clearances on all sides for maintenance and
inspection, as well as maintain minimum distances from
combustible surfaces.
TOP:
6 inches (15 cm)
EXHAUST SIDE:
6 inches (15 cm) from
surface of the exhaust vent
HEADER SIDE:
6 inches (15 cm)
DOOR PANELS:
6 inches (15 cm)
Minimum Clearances for combustible surfaces
The following minimum clearances must be maintained from combustible surfaces during operation.
Installation Requirements
In
Model
Min gpm (lpm)
Max gpm (lpm)
200
30 (114)
120 (454)
260
30 (114)
120 (454)
330
30 (114)
120 (454)
400
30 (114)
120 (454)
7