background image

JXi Troubleshooting Guide

 

Note: If the Blower runs continuously, unplug F1/F2 connector from the Ignition Control, if the Blower goes off replace the Ignition Control. Of 

the Blower stays on, check for shorted wires between the Ignition Control and PDB or from the PDB and the Blower.

 

Service Codes

 

DISPLAY FUALT 

CAUSE 

REMEDY 

Fault- Pump 

1.  Pump is not running

1. This is a normal display when the control is in Maintain Temp 

mode.  NO SERVICE REQUIRED.

NO FLOW 

1. Pump is not running
2. Low pump pressure.
3. Pressure switch fault

1.

Check breakers and power source, recheck wiring , set time
clock and current time.

2.

Clean filter, clear blockages, check position of all valves in 
plumbing system

3.

Adjust or replace pressure switch.  Refer to qualified service
personnel.

FAULT – 

HIGH 
LIMIT 

1. Water Temperature in heater 

exceeds the Internal limit.

2. Limit switch fault.

1.

Verify  function  of  high  limit  switches.   Perform  temperature
rise test. Identify and correct cause of overheating.

2.

Identify   loose   connections   or   replace   switches.     Refer   to
qualified Service Personnel.

FAULT- 

FUSELINK/FIEL
D

1.  Vent Limit fault.

1. Identify  loose  connections  or  replace  Vent Limit.    Refer  to

qualified Service Personnel.

FAULT- 
CHECK 
IGN 
CONTROL 

1. Broken, split, pinched or

disconnected fan/switch tubing.

2. Fan not operating.
3. Fan running slow or premature fan 

failure.

4. Air flow restricted at intake or 

discharge.

5. Oscillating pump pressure.
6. Low gas supply pressure.
7. No flame at burners.

1.

Check tubing and replace if necessary.

2.

Correct fault or replace fan. Refer to qualified service
personnel.

3.

Verify proper wiring for 120 or 240 VAC.  Refer to qualified 
service personnel.

4.

Check for proper clearances around heater and for adequate
room ventilation if enclosed.  Inspect for blockages or 
restriction at discharge of flue.  Refer to qualified service
personnel.

5.

Clean filter or identify and repair cause of pump oscillation.

6.

Identify and correct loose wiring connections, or problems with
igniter, flame sensor, gas valve, or ignition control.  Refer to
qualified service personnel.

Fault- 
Shorted H2O 
Sensor Or 
Open Water Sensor 

1.

 

aulty wiring or connection.

2.

 

Failed sensor.

1.

 

Inspect sensor wiring. Ensure sensor is connected into Power

Interface Board. 

2.

 

Replace temperature sensor. Refer to qualified service

personnel. 

N

O

 

Blower is ON – Start on 

Step 13

 

STEP 13- 

Check Air Pressure Switch 

24 VAC between Orange (NO) wire at the Air 
Pressure Switch and Yellow (1) wire on Transformer? 

YES

 

STEP 14- 

Check Power to PSW

 

N

O

 

24 VAC between Orange (12) wire at the Ignition 
Control and Yellow (1) wire on Transformer? 

YES

 

STEP 15

- Check Hot Surface Igniter

 

N

O

 

After Blower comes on wait at least 15 seconds 
(pre-Purge). Is Igniter glowing? 

YES

 

STEP 16- 

Check for Ignition 

N

O

 

After the HIS begins to glow, wait approximately 
40 seconds. Did the burners ignite? 

Make certain Blower s on and combustion chamber is sealed. Check air tubes for kinks or 
holes. Make certain front air tube is connected to the positive (+) side and back/lower air 
tube is connected to negative (-) side of the Air Pressure Switch. If all are OK replace the 
Air Pressure Switch. 

Check wire connections. Replace Orange wire. 

Check voltage between K and J of the Ignition Control. If 105 to 130 VAC, check wires and 
connectors to the Igniter, if OK, replace Igniter. If voltage is less than 105 VAC check 
incoming voltage between L1 and L2, if voltage is 105 to 130 VAC replace Ignition Control. 

Check voltage on Brown (13) wire at terminal VAL of the Ignition Control. Is there 24 VAC at VAL? 

N

YES

 

YES

 

Replace Ignition Control. 

Check supply gas pressure. If OK, 
replace Gas Valve. 

STEP 17- 

Check Burners operation

 

Do Burners stay on beyond 7 
seconds? 

YES

 

Step 18 – 

Verify heating

 

Heater is operating properly. 

Heater is not recognizing the flame (flame rectification). Any of the following can prevent flame rectification: 

Low gas pressure.

Poorly connected or missing ground wire.

Corroded or dirty Flame Sense Rod.

Ignition Control not sending flame sense signal.

Or there is insufficient current when the gas valve is powered. Current loss can be caused by any of the following:

Excessive corrosion on wire terminals.

Frayed or over heated wires.

Pitting contact points, usually at the Water Pressure Switch or High Limits.
To determine whether the problem is lack or rectification or loss or current, check voltage at the Black/Yellow(11) wire at 
Ignition Control. Keep the meter probe at this location and watch the reading. If, after the gas valve receives power, the
voltage slowly drops until the gas valve shuts off, then returns to normal, the problem is due to loss of current.

Flow Rates (gpm)

 

BTUs  MIN 

MAX

 

GAS PRESSURE

 

Inches of Water Column 

Natural 

LP

 

Max Inlet 

10.5 

14 

Min Inlet 

Gas Offset 

-0.2 

-0.2 

200

 

20

 

120

 

260

 

25

 

120

 

330

 

30

 

120

 

400

 

40

 

120

 

Содержание JXI200N

Страница 1: ...1 Workbook JXi Pool Spa Heater...

Страница 2: ...2...

Страница 3: ...______________________________________________ ext _________ ______________________________________________________________________ ext _________ ______________________________________________________...

Страница 4: ...to supply gas from the meter to the heater Gas shut off valve ball cock must be installed in line outside of the heater jacket Suitable gas union must be installed to connect gas line to heater outsi...

Страница 5: ...Code CSA C22 1 unless local code requirements indicate otherwise The heater comes factory wired intended for use with 240 Vot 60 Hz AC field electrical supply To use 120 Vot 60 Hz AC requires changing...

Страница 6: ...tem reduces hydraulic resistance by up to 50 versus other equipment sets in its class The Versa Plumb System s increased hydraulic efficiency allows for up to a 1 2 HP smaller pump to achieve the same...

Страница 7: ...rovide clearances on all sides for maintenance and inspection as well as maintain minimum distances from combustible surfaces TOP 6 inches 15 cm EXHAUST SIDE 6 inches 15 cm from surface of the exhaust...

Страница 8: ...other opening to living structure Dimension A 4 minimum Forced air inlet C B Distance from heater to forced air inlet or other vented opening Dimension B May be any distance if dimension C is 3 or mor...

Страница 9: ...t Length vertical or horizontal in feet metres 200 4 10cm TBD m 260 4 10cm 50 15m 330 4 10cm TBD m 400 4 10cm 50 15m Table 3 Category III Vent Pipe Sizing Table When the installation requires horizont...

Страница 10: ...uctions from the vent connector or elbow component manufacturer Figure 2 Remove Exhaust Body and Rain Shield Figure 1 Figure 2 Figure 2 Remove Exhaust Body and Rain Shield 4 Wipe the socket of the ven...

Страница 11: ...aLink RS One way is to connect at the Pool and Common terminals of the Power Interface Board This type of connection is shown on the next page The other way is to connect to the RS 485 line red termin...

Страница 12: ...ELECT SERVICE SETUP REMO TE SELECT SERVICE SETUP REMOTE TSTAT REMOTE TSTAT ENABL ED JXi HEATER CONNECTION AT FIREMAN S SWITCH At the JXi Power Interface Board connect one end of two wires to terminals...

Страница 13: ...Louver Remote Load Defaults Water Temp Cal Water Temp Diff Statistics 0 00 to 2 00 Hours Off Hi Lo Com Remote T Stat Off On 34 42 Disable Enable No Yes C or 2 F or 4 F C 1 to 5 Gas Valve on time of ho...

Страница 14: ...valve is also incorporated into this heater in the Inlet Outlet header Its purpose is to hold water in the exchanger during initial heat up to reduce the amount of condensate created at the heat exch...

Страница 15: ...Power Distribution Board Power InterfaceBoard Ignition Control Release Button Components Electrical Raceway Release Button Press to release 15...

Страница 16: ...Power Interface Board PIB R0458200 Power Distribution Circuit Board P N R0458100 To covert from 240 VAC to 120 VAC wiring snip the wire tie holding the conversion board in place Remove the conversion...

Страница 17: ...ve To HSI outof phase with 120 VAC Pre Purge 15 Sec Ignition 7 Sec Interpurge 15 Sec Heat Up 40 Sec Input 24 VAC 50 60 Hz 300 mA Valve 24 VAC 2 0 A max Inducer 120 240 VAC 3 0 A HP Ignitor 120 VAC 5 0...

Страница 18: ...ry When connected to the Power Distribution Board this transformer provides 120 VAC to terminals L1 and L2 of the Ignition Control whether the incoming power is 120 or 240 VAC The secondary 24 VAC of...

Страница 19: ...High Limit 150 F High Limit 135 F High Limit Temperature Sensors Kit R0592300 High Limit 135 F High Limit 150 F 19...

Страница 20: ...Air Blower Air Pressure Switch Air Orifice Union Gas Orifice is located here Gas Valve Fuel Components 20...

Страница 21: ...ORIFACE KIT BTU NATURAL LP 200 R0591302 R0591312 260 R0591303 R0591313 330 R0591304 R0591314 400 R0591305 R0591315 FUEL ORIFACE KIT BTU NATURAL LP 200 R0591601 R0591605 260 R0591602 R0591606 330 R0591...

Страница 22: ...Air Pressure Switch R0456400 Gas Valve R0591400 Hot Surface Igniter HSI R0457500 Range 50 to 500 Ohms 22...

Страница 23: ...Exhaust Temperature Switch R0524300 Burner R0591700 23...

Страница 24: ...ow 10 replace PIB YES STEP 4 Check power to Water Press Sw 24 VAC between Purple 4 wire on PIB NO and Yellow 1 wire on Transformer Recheck at Red 3 wire if voltage is 24 VAC replace PIB 24 VAC between...

Страница 25: ...ice personnel NO Blower is ON Start on Step 13 STEP 13 Check Air Pressure Switch 24 VAC between Orange NO wire at the Air Pressure Switch and Yellow 1 wire on Transformer YES STEP 14 Check Power to PS...

Страница 26: ......

Отзывы: