background image

19

EE02

Low pressure protection

Low-pressure sensor broken.

 Replace the low-pressure sensor.

Insufficient level of refrigerant.

 Add refrigerant.

Ambient temperature and input 

water temperature too low.

Send the pump to the retailer for a 

detailed inspection.

EE03

Water flow rate protection

Flow switch incorrectly positioned.

 Re-make the connections.

Insufficient water flow.

Increase the water flow rate.

Broken flow switch.

 Replace the flow switch.

Faulty filter pump.

Repair or replace the filter pump.

EE04

In heating mode, temperature 

overheating error 

In heating mode, temperature 

overheating error.

Check that the flow rate is sufficient.

Faulty flow switch.

 

Replace the flow switch.

Abnormal d2-TH5 sensor reading.

 

Replace the d2-TH5 sensor.

EE05

d6-TH3 exhaust temperature protection

Insufficient refrigerant.

 Check for the presence of gas 

leaks and add refrigerant.

Insufficient water flow rate.

Check the by-pass valve.

Clogged filter or electronic valve.

 

Check refrigerant levels.

d6-TH3 sensor fault.

 

Check the d6-TH3 sensor.

EE06

Controller fault

The connection is faulty.

 Check the connection.
 Replace the cable.

The controller is faulty.

 Replace the controller.

EE07

Compressor protection

The connection is faulty.

 Check the connection.

Accumulation of liquid and gas.

 Check the power supply voltages

Faulty compressor or printed circuit 

board.

 Check the phases.

Abnormal water flow rate.

 Check the water flow rate.

Fluctuating power supply.

Check the electrical grid.

EE08

Communication error between the 

controller and the power board

The connection is faulty.

 Check the connection.
 Replace the cable.

The controller is faulty.

 Replace the controller.

EE09

Communication error between the 

controller and the control board.

The connection is faulty.

 Check the connection.
 Replace the cable.

The controller is faulty.

 Replace the controller.

EE10

High voltage protection

Voltage too high.

 

Check the voltage.

Faulty power board.

 

Replace the power board and/or 

control board.

Содержание HPO

Страница 1: ...H0721600_REVA 2021 05 HPO EN Instructions for installation and use English Heat pump Translation of the original instructions in French More documents on www zodiac com...

Страница 2: ...the risk of injury occurring when working on the appliance Before handling the appliance check that it is switched off and isolated The appliance is intended to be used for pools and spas for a speci...

Страница 3: ...pply and that all other equipment or accessories connected to the appliance are also disconnected from the power circuit Do not disconnect and reconnect the appliance to the power supply when in opera...

Страница 4: ...ing maintenance work ensure there are no traces of corrosion or oil around the cooling components Before beginning work on the cooling circuit stop the appliance and wait for a few minutes before fitt...

Страница 5: ...t be compatible for use with the refrigerant concerned including where appropriate a flammable refrigerant Moreover a set of calibrated scales must be available and in good working order The pipework...

Страница 6: ...Technical specifications 25 5 3 I Dimensions and marking 26 Tip to make it easier to contact the retailer Write down the retailer s contact details to help you find them more easily and fill in the pr...

Страница 7: ...or installing the anti vibration pads The appliance must not be installed With the blowing towards any permanent or temporary obstacle less than 4 metres away Within range of watering nozzles sprays o...

Страница 8: ...ss must be installed to make it easier to work on the appliance Water inlet valve By pass valve Water outlet valve Water inlet adjustment valve optional Water outlet adjustment valve optional Water tr...

Страница 9: ...installed The appliance is provided for connection to a general power supply with a TT or TN S neutral regime Electrical protection by circuit breaker D curve rating to be defined according to the ta...

Страница 10: ...said to be slaved to the heating system Filtration is kept in operation or activated if the pool temperature falls below the desired temperature For the connection connect the filtration timer to ter...

Страница 11: ...tinuous operation 24 7 To maintain the temperature throughout the season run automatic circulation for the equivalent of the water temperature divided by two the longer this time the more sufficient t...

Страница 12: ...er inlet valve By pass valve Water outlet valve Water inlet adjustment valve optional Water outlet adjustment valve optional An incorrect by pass setting may cause the heat pump to malfunction Check t...

Страница 13: ...ING COOLING operating mode is selected the heat pump automatically switches to HEATING mode if the water temperature falls 1 C below the temperature setpoint or to COOLING mode if the water temperatur...

Страница 14: ...ng requirements and silent operation desired Cooling hot zones heat waves sheltered pools etc The compressor speed directly affects the appliance s power output Press BOOST SMART or SILENCE the indica...

Страница 15: ...that the appliance undergo general servicing at least on a yearly basis to ensure its proper operation maintain performance levels and prevent any possible failures These operations are carried out a...

Страница 16: ...g maintenance work a leak detector must continuously monitor for leaks at the most critical point in order to report any potentially hazardous situation Particular attention must be paid to the follow...

Страница 17: ...is complete if this is not already the case Pay close attention to not overfilling the cooling system Before recharging the system carry out a pressure test using a suitable purge gas The system must...

Страница 18: ...e the heat pump s operating range It may be that the heat pump has detected an operating fault see 4 2 I Error code display If you have checked these points and the problem persists contact your retai...

Страница 19: ...Possible causes Solutions PP01 Faulty inlet water temperature sensor Sensor disconnected or out of order Reconnect or replace the sensor PP02 Faulty outlet water temperature sensor Sensor disconnecte...

Страница 20: ...water flow rate Check the by pass valve Clogged filter or electronic valve Check refrigerant levels d6 TH3 sensor fault Check the d6 TH3 sensor EE06 Controller fault The connection is faulty Check the...

Страница 21: ...r the propellers are broken Check the fan speed Check the propellers EE16 PFC module protection The data is incorrect Check the printed circuit board The fan motor is faulty Check the fan speed The pr...

Страница 22: ...oo low Check and replace the printed circuit board EE25 Compressor power error The compressor operates with 1 or 2 phases Check the wiring EE26 4 way valve inversion error Blockage inversion of the 4...

Страница 23: ...22 4 3 I Wiring diagramsWiring diagrams 4 3 1 HPO 6 HPO 8 HPO 9 HPO 11 HPO 14 EN...

Страница 24: ...23 4 3 2 HPO 18...

Страница 25: ...iption A HPO B 50 PVC connectors x2 C Anti vibration pads x4 D Winterising cover Heating priority E Remote control kit F Condensate drainage connector x2 G Hose x2 H PAC NET cleaning product Included...

Страница 26: ...3 x 2 5 3 x 4 3G1 5 3G2 5 3G4 Max suction discharge pressure bar 45 Max low pressure high pressure side bar 25 Recommended water flow m h 4 5 6 7 8 10 Sound pressure at 10m max min db A 34 22 36 23 3...

Страница 27: ...d marking Grid User interface Pool water inlet Pool water outlet Front Rear Top Bottom Model HPO 6 HPO 8 HPO 9 HPO 11 HPO 14 HPO 18 A 859 985 1074 B 641 736 941 C 357 357 395 D 97 97 107 E 446 5 537 7...

Страница 28: ...diac Pool Systems LLC All rights reserved ZODIAC is a registered trademark of Zodiac International S A S U used under license All other trademarks are the property of their respective owners ZPCE ZA L...

Отзывы: