5
1.3.2 Installation requirements
1.3.3 Connection to surrounding air
Leave sufficient space to install a blower plenum* on top of the unit in order to orient the air flow, if
possible towards the bay windows opening on the exterior.
*unit distributing air to the blowing system
1)
Install the appliance on a level base,
to avoid any overflows from the condensation
tray,
2)
Easy access
to the appliance for maintenance and connections, leave
1 meter of free space around the CAE.
3)
Place nothing in front of or on the blowing and suction grates
,
4)
Anti-vibration studs
(supplied)
must be installed
under the appliance,
5) For a
swimming pool building with a high ceiling or visible roof frame
:
- destratification of the upper layers of the room = one or several fans with PVC
blades
or
an air extractor with fresh air intake.
Warning!
230 V AC appliances = must be outside volume 1 (see §1.3.1),
6)
Building requirements:
swimming pool building = very damp room
During building make sure that:
- the materials used are compatible with a swimming pool environment,
- the walls are sufficiently waterproofed and insulated to avoid condensation forming in
the room when relative humidity reaches 60 to 70%.
Light structure buildings (verandas, shelters...): there is no risk of deterioration of the
structure, even in case of dew as they are designed to support this (even with a relative
humidity of 70%)
7)
Risk of stratification:
- height of the room < 4 to 5 meters: mechanical ventilator unit or extractor,
- height of the room > 7 to 8 meters: ceiling fans with large blades,
8)
Ventilation,
renewal of air,
- private pools: highly recommended
- public pools: compulsory
The air can be renewed by:
- a simple mechanical ventilation unit,
- a wall or roof extractor with fresh air intakes.
This ventilation ensures the hygienic renewal of air, the removal of any chloramines
present in the air, and the elimination of excessively hot air, whilst contributing to the
dehumidification of the room.
* minimum distance
CAE 508-510-513
extractor grate
double deflector
grate
Hygro Control
fresh air intake
air renewal
system (see §1.3.2)
condensation
drainage
air flow box
suction
blowing
Pool
Содержание CAE
Страница 1: ...Air dehumidifier for indoor swimming pools R f N D 006 A 1 Ver 02 2010 CAE Installation instructions...
Страница 22: ...1 Sch ma lectrique Sch ma de puissance CAE 508 510 513...
Страница 23: ...2 Sch ma de commande CAE 508 510 513...
Страница 25: ...4 Dimensions weight without option Kg CAE 508 228 CAE 510 235 CAE 513 240...
Страница 26: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...
Страница 27: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...