P a g e
|
13
16.
16. Attach the terminal cap (see Figure 17 ).
3.4
Wiring the Power Pack to Power Source
WARNING
When using electrical products, basic precautions should always be followed, including the following:
•
DANGER: RISK OF ELECTRIC SHOCK WHICH CAN RESULT IN SERIOUS INJURY OR DEATH. Before
attempting installation or service, ensure that all power to the device is disconnected/turned off at the circuit breaker.
Connect only to a circuit protected by a ground-fault circuit-interrupter (GFCI).
•
Grounding is required. The unit should be installed by a qualified service representative and should be properly
grounded and bonded (See Section 3.5, Bonding).
•
To avoid property damage, serious injury or death, never use the chassis backplate of the power pack to ground any
other equipment.
•
Install to permit access for servicing.
•Please read all cautions and safety instructions in the Important Safety Instructions section.
Before attempting any
electrical wiring, be sure to read and follow safety instructions. Wiring should only be attempted by a qualified
professional.
1.
Wire power pack to pool pump power source using 3.3 mm
2
(12 AWG) insulated wire and conduit. Wire the power
pack to the LOAD side of a pump or the LOAD side of the pool pump timer relay so that the chlorinator can only
come on when the pool pump comes on (see Figure 18).
2.
Attach the third wire (ground) from the electrical panel to the ground point inside the power pack. Additionally,
applicable local and/or National installation codes may require the equipment to be properly bonded to other pool
equipment or to a bonding grid. Bonding per Section 3.5 must also be accomplished to ensure personal safety and
safety of equipment.
3.5
Bonding
Canadian Electric Code (CEC) requires pool equipment to be bonded to each other. Check your local codes to determine
if other local installation codes are enforced by the Authority Having Jurisdiction (AHJ). A solid, copper 8.37 mm
2
(8
AWG) wire is recommended, per the CEC, for bonding the power pack to a permanent bonding connection that is
acceptable to the local AHJ. Refer to your locally enforced codes for the acceptable bonding wire gauge. Attach the
bonding point located on the bottom of the chassis backplate to a common bonding point. Do not use the power pack as
the common bonding point. Each piece of non-related pool equipment requiring a ground should also be bonded to the
common, approved bonding point. There should be one bonding connection to the power pack. CEC dictates that the
bonding conductor be, minimum 13.3 mm
2
(6 AWG).
3.6
Connection to an AquaLink RS Control System or PDA (Optional)
The AquaLink RS or PDA is a multi-function pool controller which can fully control the function of the Zodiac AquaPure
Ei Series APURE35C chlorine generating device. Adjustment of the chlorine production rate can be controlled from the
main menu of the AquaLink RS or PDA. The AquaLink RS or PDA offers individual pool and spa settings for output
percentage. Refer to the AquaLink RS or PDA Owner’s Manual for more information.
NOTE
The Zodiac AquaPure Ei Series APURE35C chlorine generating device will communicate with
all AquaLink models Rev. K or later.
Содержание APURE35C
Страница 35: ......