Pay attention to the direction of the wire when installing the modules. It should be connected along the wire 

direction to avoid bending the wire.  

2

Electrical Connection

 

The  Direct  Current  (DC)  generated  by  the  PV  system  can  be  converted  to  Alternating  Current  (AC)  and 

connected to the public power grid. Different regions may have different policies, laws and regulations to stipulate 
the  installation  and  grid-connection  requirements  of  PV  systems.  Therefore,  during  the  design,  installation  and 
grid-connection of PV system, please comply with the local policies, laws and regulations. 

PV  modules  can  obtain  different  current  and  voltage  outputs  through  series  connection  and  parallel 

connection. Read this installation manual carefully before electrical connection and installation. Please design and 
connect according to the current and voltage required by customers. Before connection, please ensure that the 
connection part is free from corrosion, and keep it clean and dry. 

Different types  of  modules  cannot be  connected  in  series.  Modules  connected  in  series  should  ensure  the 

consistency  of  their  current.  The  voltage  of  the  module  string  should  not  exceed  the  allowable  system  voltage 
value, which can be found on the nameplate or datasheet of the module. 

ZNSHINE  SOLAR  modules are  provided with  stranded  copper cables  with  a  cross  sectional area  of  4mm² 

which  are  UV  resistant.  All  other  cables  used  to  connect  the  DC  system  should  have  a  similar  (or  better) 
specification.  

The maximum number of modules in series depends on the system design, the type of converter used and 

the environmental conditions. In general, the maximum number (N) of PV modules in series can be calculated by 
dividing  the  maximum  system  voltage  by  the  open  circuit  voltage  of  the  relevant  solar  PV  modules.  When 
designing the solar PV system, it is necessary to take into account the characteristic that the voltage of the solar 
PV  module  changes  with  the  temperature.  Considering  the  voltage  increase  caused  by  temperature  drop  in 
extreme environment in winter, the maximum series connection number of solar PV modules can be calculated by 
the following formula. 

Table 5-4  maximum series connection number calculation 

Formula 

Maximum system voltage V 

 N

*

V

oc

*

[1+β

*

(T

min

 -

25)] 

Maximum system voltage 

The number of maximum solar PV modules in series 

V

oc

 

The open circuit voltage of each module (see product label or datasheet) 

β

 

Temperature coefficient of open circuit voltage of the module (refer to datasheet) 

T

min

 

The lowest ambient temperature at installation site 

If the modules are allowed to be installed in parallel electrically, each module (or series string of modules so 

connected) shall be provided with the maximum series fuse as specified. For applications requiring high currents, 
several  photovoltaic  modules  can  be  connected  in  parallel;  the  total  current  is  equal  to  the  sum  of  individual 
currents, each module (or series string of modules so connected) shall be provided with the maximum series fuse 
as specified. The recommended number of module in parallel is only one. The modules’ electrical performance in 
a system is the same. When connected in series, all modules must have the same amperage. When connected in 
parallel,  the  modules  must  all  have  the  same  voltage.  Connect  the  quantity  of  modules  that  match  the  voltage 
specifications of the devices used in the system. The modules must not be connected together to create a voltage 
that is higher than the permitted system voltage. 

Product  can  be  irreparably  damaged  if  an  array  string  is  connected  in  reverse  polarity  to  another.  Always 

verify  the  voltage  and  polarity  of  each  individual  string  before  making  a  parallel  connection.  If  you  measure  a 
reversed  polarity  or  a  difference  of  more  than  10V  between  strings  then  check  the    string  configuration  before 
making the connection. 

Before wiring the module, ensure that the contact points are corrosion resistant, clean and dry; If a string of 

modules is reversed, irreparable damage can be caused. 

Each ZNSHINE SOLAR PV module has two PV cables which can withstand 85

 temperature and they are 

sunlight  resistant(UV).  The  cross-sectional  area  of  the  cable  is  4mm²  or  12AWG,  and  the  external  diameter  is 
5mm

7mm. The minimum bending radius of the cables must be 43mm. Any cable damage caused by bending 

too  much  or  cable  management  system  is  not  covered  under  ZNSHINE  SOLAR’s  warranty.  Plug  &  Play 
connectors are included at the end of each cable. All other cables used to connect the direct current system shall 

Содержание ZXM6-HD 120-330/M

Страница 1: ...S INSTALLATION MANUAL Double glass Bifacial double glass Modules ZNSHINE PV TECH CO LTD No 1 South Zhenxing Road Zhixi Town Industry Concentration Zone Jintan Zone Changzhou Jiangsu Province China Tel...

Страница 2: ...ZX RD III032A DOCUMENT COUNTERSIGN DEPARTMENT Product Technology Department Quality Department Marketing Center COUNTERSIGNER DOCUMENT NO QES ZX RD 032A COMPILER EDITION A REVIEWER EFFECTIVE DATE 2020...

Страница 3: ...STORAGE 7 4 UNPACKING SAFETY 7 5 INSTALLATION 8 5 1 INSTALLATION SAFETY 8 5 2 ENVIRONMENT CONDITIONS AND SITE SELECTION 9 5 3 TILT ANGLE OF INSTALLATION 10 5 4 INSTALLATION REQUIREMENTS FOR BIFACIAL...

Страница 4: ...ions and suggestions Do not constitute a warranty expresses or implied 1 2 LIMITATION OF LIABILITY ZNSHINE SOLAR is not responsible for any form of damage including but not limited to module operation...

Страница 5: ...on the module directly 2 Do not damage or scratch the front or backside surfaces of the module 3 Do not drag Scratch bend the output cable with force or with too tight connection The insulation of out...

Страница 6: ...by two or more persons at the same time 5 Handling the modules requires two or more people with nonslip gloves and both hands 6 Do not lift modules by their wires or junction box 7 Do not handle the m...

Страница 7: ...e 3 1 3 Modules in carton are fragile which must be handled with care 3 1 4 The packaging must be transported upright 3 1 5 Do not step on the package and module 3 1 6 Modules shall be stacked as requ...

Страница 8: ...ropes are strong and firm Two people shall support at the two sides of the righting carton gently to place it on the relatively flat position of the project site 3 2 2 Use a forklift to remove the mo...

Страница 9: ...ea or air During transportation make sure that the package is fixed securely to the shipping platform without movement Do not Stack more than two layers on truck 3 3 3 Only one layer stacking is only...

Страница 10: ...npacking outdoors it is prohibited to operate in rainy conditions Because the carton will become soft and damaged after it gets wet in the rain The stacked PV modules hereinafter referred to as module...

Страница 11: ...he connector if the system circuit is connected to a load 11 Do not stand on the module glass There is a risk of injury or electric shock if glass is broken 12 Do not work alone always work as a team...

Страница 12: ...lowest position on the horizon in winter The shadow will cause the loss of the output power of the solar photovoltaic system Although the bypass diode installed in the PV module can reduce this loss t...

Страница 13: ...rantee enough power output during the winter it will make the whole solar PV system in the rest of the year can have enough power output also PV modules are recommended to be installed at an optimized...

Страница 14: ...gain it is recommended to install the module at a height from 0 5m to 2m See Fig 5 2 Fig 5 2 Distance from the earth In the system design besides the ground type and the module installation height to...

Страница 15: ...ss steel gaskets with a minimum thickness of 1 5mm and an external diameter of 16 20mm shall be used in all parts of the components connected to the Single axis tracking system The installation method...

Страница 16: ...consulted by ZNSHINE SOLAR B Mounting with Single axis Tracking System with 4 7 10mm mounting holes Modules can be attached through the mounting holes 4 7 10mm on the back of the module frame by fixin...

Страница 17: ...e Mechanical Load Pressure Safety factor Mounting Direction 60 66 72 120 132 144 pcs double glass 60 66 72 120 132 144 pcs bifacial double glass 1600Pa 1600Pa 1 5 NOTE The above described distance is...

Страница 18: ...in the table below Figure 5 5 Mounting holes schematic of the single module for the 2V installation method Module Mechanical Load Pressure Safety factor Mounting Direction 60 66 72 120 132 144 pcs dou...

Страница 19: ...each module two clamps should be attached on each long sides of the module for portrait orientation Depending on local wind and snow loads additional clamps may be required to ensure that modules can...

Страница 20: ...o make sure the Mechanical load 4 The load is an empirical value of a standard module based on a standard installation mode and the specific information shall be consulted by ZNSHINE SOLAR 60 66 72 12...

Страница 21: ...mounting method use at least four clamps on each module the 4 clamps should be attached two each on the long sides of the module Depending on local wind and snow loads additional clamps may be require...

Страница 22: ...gth 72 144 pcs frameless bifacial double glass 1600Pa 1600Pa 1 5 150mm A 1 4L 50mm L Module length NOTE The above described distances are from the module edge to the middle of the clamp Need two or mo...

Страница 23: ...V modules Insert the PV module into the clamp and make sure the module edge touch to the EPDM closely and then tighten the nut with uniform torque values using a q qualified torque wrench Ensure the m...

Страница 24: ...J Box are as follows The extension cable is required Fig 1 Split J Box at module side position for vertical direction Fig 2 Split J Box at module middle position for vertical direction Fig 3 Split J B...

Страница 25: ...he following formula Table 5 4 maximum series connection number calculation Formula Maximum system voltage V N Voc 1 Tmin 25 V Maximum system voltage N The number of maximum solar PV modules in series...

Страница 26: ...e calculated by the following formula Minimum current carrying capacity of the cable 1 25 Isc Np Isc short circuit current of PV module unit A Np the number of modules in parallel or module strings If...

Страница 27: ...and meet the requirements of the national electrical code It is recommended to use the copper wire 4 14mm2 or AWG 6 12 as the grounding wire The signal can be found at the grounding hole position The...

Страница 28: ...igh voltages this is dangerous Please pay attention to safety when maintenance and it must be done by professionals Wear cut resistant gloves and other personal protective equipment required for the p...

Страница 29: ...se a soft cloth together with a mild detergent and clean water Take care to avoid severe thermal shocks which might damage the module by cleaning modules with water which has a similar temperature to...

Страница 30: ...urface or not 5 Check whether the module support structure is leaning or bent or not 6 Check whether the connectors of the module are detached or not 7 After cleaning fill out the PV module cleaning r...

Страница 31: ...FICATION FOR SOLAR MODULE BARCODE Example PMC placed the order for the second time in one day the 3rd workshop produced a batch of 5BB mono with coating PV modules And the 3rd workshop started product...

Страница 32: ...ZXM6 LD60 330 M 330 33 6 9 83 40 8 10 35 1678 1002 30 22 Si Mono 158 75 158 75 20 1500 Class A ZXM6 LD72 380 M 380 39 8 9 55 48 5 10 07 2000 1002 30 26 Si Mono 158 75 158 75 20 1500 Class A ZXM6 LD72...

Страница 33: ...91 49 4 13 65 2256 1133 35 33 5 Si Mono 182 91 25 1500 Class A ZXM7 SPLDD144 535 M 535 41 3 12 96 49 6 13 71 2256 1133 35 33 5 Si Mono 182 91 25 1500 Class A ZXM7 SPLDD144 540 M 540 41 5 13 02 49 8 13...

Страница 34: ...www znshinesolar com Document No QES ZX RD III032A 31 9 Modify record Revision Date Version No Revisioner Remarks modifications chapters etc New 2020 10 13 A Full text of Installation Manual...

Отзывы: