XPLC108E Motion Controller User Manual V1.5
Voltage level
DC24V
Max output current
+300mA (the max output current of OUT28-
OUT31 is 500mA)
Max leakage current when off
25μA
Respond time to conduct
12μs
Respond time to close
80μs
Overcurrent protection
Support
Isolation method
Photoelectric isolation
Note:
The times in the form are typical based on the resistive load, and may change
when the load circuit changes.
Due to the leak-type output, the shutdown of the output will be obviously
affected by the external load circuit, and the output frequency should not be set
too high in the application.
→
Wiring Reference
→
Wiring Note:
⚫
The wiring principle of digital output OUT (0-31) is shown in the figure above. The
external signal receiving end can be an optocoupler or a relay or solenoid valve, all
can be connected as long as the input current does not exceed 300mA.
⚫
For the connection of the public end, please connect the "EGND" port on the IO power
supply to the negative pole of the DC power supply of the external input device. If the
Содержание XPLC108E