Pelletherm V.2 M01 44
It is forbidden to stop the boiler through switch "POWER" during operation!
6.4.1. STOPPING THE BOILER THROUGH "START" SWITCH.
Boiler is switched on in operating mode and respectively switched off through "START"
switch (which is on the interface control panel of the equipment). Upon switching off at its
display is showing message "
FINAL COMBUSTION
" (final burning out).
Figure 6.14. "START" switch mounted on the interface panel of the boiler.
Switching off the boiler should be done only by the key "START" and not by stopping the
power supply of the equipment. The reason is that by stopping by the key "START" there is
carried out a controlled shutdown process where there is cooling of the equipment, it is
performed full burning out of the fuel and is kept the reliability of the equipment.
Switching off the boiler is made by returning the key "START" in initial position - "off". This is
the recommended way of switching off, as there is done the so called "controlled shutdown"
during which the concerned fans are working and emergency signals are monitored by the
boiler controller. After cooling, the boiler must be switched off via the key "POWER", which is
located on the control panel of the equipment.
6.4.2. STOPPING THE BOILER THROUGH MENU ON THE CONTROLLER KEYPAD.
To stop the pellet boiler "Pelletherm V.2 M01" it is necessary to have effect on the boiler
operation through the following actions:
To press for long (more than 5 sec.) the button "ESC";
To select answer "YES" in the appearance of the query, appeared on the display -
"
Make final combustion
?".
Choice for stopping the boiler "Pelletherm V.2 M01" is shown by the inscription "
Final
combustion
" (final burning out) and should stop the boiler operation.
There is another approach to stop the boiler operation: using the menu "
MAKE FINAL
COMB
." from the controller of the equipment.
This option is used to stop the operation of the boiler, for can make final
burning out of the fuel contained in the grate of the specialized burner.
Despite these opportunities, we recommend stopping to be made from the
switch "Start"!