Pelletherm V.2 M01 32
Figure 6.3. Designation of the electrical connectors mounted on the interface panel of the
boiler.
The elements of the interface panel and their functions are as follows:
Connector - Flue gases fan;
Connector – Hall sensor;
Connector - Emergency thermostat 100
0
H
2
O;
Connector - "NTC" sensor.
Emergency thermostat - protects the hot-water pellet boiler from overheating.
The thermostat is factory-set to stop power supply of the boiler in excess of
the circulating water temperature in the boiler body above limit (set in the
manufacturer’s factory at 100
o
C).
Remove the bridge when using room thermostat! Use only the contact of the
room thermostat. Do not put external voltage! See the wiring diagram!
Control module has built-in protection against exceeding the temperature of
the circulating water in the boiler body over limit value of 95
o
C. Upon reaching
this temperature, a message for overheating is displayed. The emergency
thermostat set at 100
o
C is an additional protection.
All work on the electrical installation of the boiler, making of settings where are
removed covers and other elements that protect against contact with live
parts, should only be performed by a qualified person.
Flue gases fan
„NTC” sensor
Emergency
thermostat
Hall sensor