The 0–F bits of the rotary DIP switch indicate device numbers 1–16 during RS485 communication. (Switch 0 indicates device number 16, switch 1 
indicates device number 1, and so on. Switch F indicates device number 15). You can rotate the 0–F bits of the rotary DIP switch to 
corresponding positions to set device numbers, and then restart the control panel to make the setting take effect. Address numbers cannot be 
repetitive. 
 

 

 
1) Control panel provides lock control output interfaces. For NO lock, it is open when power is on, and closed when power is off, so COM and NO 

interfaces should be used. For NC lock, it is open when power is off, and closed when power is on, so COM and NC interfaces should be used. 

2) The default connection mode of the door lock is “dry mode”. Specifically, the electrical lock uses an external power supply separately, rather 

than share the power supply for the control panel. 

3) Our access controller is powered by standard PoE or access control power. You can choose either of the two power supplies as needed. The 

two power supplies provide 12V/3A power for only the power consumption of the control panel, Wiegand readers, and output power 
consumption of RS485 reader. 

4) When the Electrical Lock is connected to the Access Control System, you need to parallel one FR107 diode (equipped in the package) to 

prevent the self-inductance EMF affecting the system, do not reverse the polarities. 

5) The following figure shows the default lock connection mode. 

    

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 

The control panel supports RS485 reader and Wiegand reader (Note: The control panel does not support fingerprint verification of RS485 reader). 
RS485 reader connection: First of all, set the RS485 address (device number) of the reader by DIP switch or other ways. The RS485 address 1 is for 
Door 1 IN reader, RS485 address 2 is for Door 1 OUT reader, RS485 address 3 is for Door 2 IN reader, RS485 address 4 is for Door 2 OUT reader, as in 
the figure below. 

 

 

 
 
 
 
 
 
 
 
 
 
 

 

Besides, a single EXT RS485 interface can supply maximum 750 mA (12V) current. So the entire current consumption should be less than this max 
value when the readers share power with the panel.    In calculation, please use max current of the reader, and start current is usually more than 
twice of the normal work current, please consider of this situation.   

5. DIP Switch Settings 

6. Connection Of Lock 

NC Lock 

NO Lock 

Lock 

Lock 

 

Diode 

Diode 

Power 

Input 

Enlarged 

diagram 

of lock ports 

Power 

Input 

 

“Dry mode” wiring diagram of lock connecting   

with external power supply(recommend) 

7. RS485 Reader Connection 

PC 

4# Reader 3# Reader 2# Reader 1# Reader 

+12V 

GND 

485B 

485A 

TCP/IP 