BG300 Barrier Gate
User Manual
P a g e
|
2 3
Copyright©2022 ZKTECO CO., LTD. All rights reserved.
9
Commissioning Instructions
1.
Check all the connections and make sure the connections are correct before connecting to
the power supply.
2.
Please use the remote control or press the switch button on the mainboard to test whether
the machine is running normally. (Warning: Be sure to install the corresponding length of
the boom before the power-on test. To avoid accidents, no one is allowed to stand under
the boom during debugging. )
3.
In the process of boom falling, short connect the infrared detector and public interface,
the falling boom is transferred to rising immediately, which will stop automatically after
the rising limit.
4.
In the process of boom falling, short connect the loop detector and public interface, the
falling boom is transferred to rising immediately, which will fall automatically after the
rising limit and stop automatically after the falling limit. In the process of boom rising,
short connect the loop detector and public interface, the boom will fall automatically after
the rising limit and stop automatically after the falling limit. In the open state, short
connect the loop detector and public interface, the boom will automatically fall to the limit
and stop.
5.
Left and right movement interchange method:
BG300 Barrier gate left and right movement interchange: