Chapter 1: System wiring
8
ZP3-ECU Extinguishing Control Unit Installation and Commissioning Manual
Programming on a zone basis
The ECU shown in diagram 5 of Figure 4 on page 7 is configured for its first
address to be 1005 and its second address to be 2025.
Diagram 1:
• Zone 1 consists of detector 1001 (coincidence area one)
• Zone 2 consists of detector 2001 (coincidence area two)
Diagram 3:
• Zone 1 consists of detectors 1001, 1002, and 1003 (coincidence area one)
• Zone 2 consists of detectors 2001, 2002, and 2003 (coincidence area two)
Both areas are programmed identically.
Input
Output
Mode
Zone 1
1005 (ECU FIRST ADDRESS)
SKNS (Single knock non silencing)
Zone 2
2025 (ECU SECOND ADDRESS)
SKNS (Single knock non silencing)