Chapter 1: System wiring
ZP3-ECU Extinguishing Control Unit Installation and Commissioning Manual
9
Programming on a device basis
The ECU shown in diagram 5 of Figure 4 on page 7, is configured for its first
address to be 1005 and its second address to be 2025.
Diagram 1:
• Coincidence area one consists of device 1001
• Coincidence area two consists of device 2001
Diagram 3:
• Coincidence area one consists of devices 1001, 1002, and 1003
• Coincidence area two consists of devices 2001, 2002, and 2003
Both areas are programmed in a similar manner:
Diagram 1
Input
Output
Mode
1001
1005 (ECU FIRST ADDRESS)
SKNS (Single knock non silencing)
2001
2025 (ECU SECOND ADDRESS)
SKNS (Single knock non silencing)
Diagram 3
Input
Output
Mode
1001
1005 (ECU FIRST ADDRESS)
SKNS (Single knock non silencing)
1002
1005 (ECU FIRST ADDRESS)
SKNS (Single knock non silencing)
1003
1005 (ECU FIRST ADDRESS)
SKNS (Single knock non silencing)
2001
2025 (ECU SECOND ADDRESS)
SKNS (Single knock non silencing)
2002
2025 (ECU SECOND ADDRESS)
SKNS (Single knock non silencing)
2003
2025 (ECU SECOND ADDRESS)
SKNS (Single knock non silencing)
The same format and rules apply for any protected area.