Functions and operation 

Danger:

  Before  connecting  the  power  supply,  make  sure  that  the  water  tank,  solar  collector,  solar 

pumping station and all temperature sensors are good connected! 

Note:

 For safety, auxiliary heating is locked at delivery state. The single 

 displays on the screen. If 

you want to use this function, please see operation: 3.5 Forbid/Permit using auxiliary heating. 

 

3.1

 

Setting time 

After power supply is switched on, please firstly set the time of the 

system. 

 

ì

 

Press 

System  Setting

  button  until  the  signal 

Week_

 

displays on the screen. 

ì

 

Press 

“ ”

 

 button to set weekday. 

ì

 

Press 

Confirm

  button  to  save  the  setting;  press 

Cancel

 

button to cancel the setting. 

 

ì

 

Press 

System  Setting

  button  again  until 

  displays  on 

the screen. 

ì

 

Press 

“ ”

 button to set hour, press 

 button to set minute. 

ì

 

Press 

Confirm

  button  to  save  the  setting;  press 

Cancel

 

button to cancel the setting. 

 

3.2

 

Temperature difference circulation function   

The solar control program works on the principle of temperature difference circulation. Solar pump P1 is triggered, 

as soon as the preset temperature difference between collector and tank is reached. 

ì

 

Press 

System Setting

 button, until 

 displays on the screen. 

ì

 

Press 

“ ”“

 button to adjust storage tank temperature. Default value: 60

, setting range: 45~75

ì

 

Press 

Confirm

 button to save the setting. Press 

Cancel

 button to cancel this function. 

ì

 

At the same time the menu shows 

10

, the default value of 

switch-on temperature difference. 

ì

 

Press 

“ ”“

 button to adjust it. Setting range: 5~20

.

 

ì

 

Press 

Confirm

  button  to  save  the  setting.  Press 

Cancel

 

button to cancel this function. 

ì

 

Then the  menu shows 

5

,    the  default  value  of switch-off 

temperature difference. 

ì

 

Press 

“ ”

 

 button to adjust it, adjustable range: 2~12

ì

 

Press 

Confirm

 button to confirm the setting. Press 

Cancel

 button to cancel the function. 

Содержание SP226

Страница 1: ......

Страница 2: ...operation is no longer possible please immediately take the device out of operation Without lightning rod please don t use this device during a thunderstorm 1 3 Liability waiver Improper installation...

Страница 3: ...or in bottom part of storage tank T3 Temperature sensor in top part of storage tank P1 Solar collector pump P2 Solar circulation pump Danger If there is only one temperature sensor in water storage ta...

Страница 4: ...Pump speed regulation 4 WILO pump 5 Input connector 6 Security valve 7 Expansion vessel connector 8 Output connector 9 Mounting point 2 2 2 Installation description SP116 should be installed in retur...

Страница 5: ...System working pressure 8 bar Safety valve response pressure 6 bar Ambient temperature 0 50 Input signals T1 T3 top part of water tank bottom part of water tank solar collector Output signals 3 auxili...

Страница 6: ...size 450mm 310mm 150mm Max own consumption 3W Range of temperature measuring NTC10K 0 99 PT1000 0 199 Accuracy of temperature measuring 1 Power of pumps solar collector pump P1 and circulation pump P...

Страница 7: ...on Setting three time periods Tank temperature As turning on off temperature value for auxiliary heating Solar system indication For SP116 SP226 only 1 system available Frost protection signal Overhea...

Страница 8: ...e Press Confirm button to save the setting press Cancel button to cancel the setting 3 2 Temperature difference circulation function The solar control program works on the principle of temperature dif...

Страница 9: ...time period Perform like above steps the other two time periods can be set Note If you want to shut off one of the three time periods you can set a same value for both start time and end time e g you...

Страница 10: ...ating Press Choose Function button until displays on the screen Press Confirm button to save the setting and forbid auxiliary heating Press Choose Function button until displays on the screen Press Ca...

Страница 11: ...the screen Press button to adjust the maximum collector temperature Default value 115 adjustable range 100 130 Press Confirm button to confirm the setting press Cancel button to quit this function 3 1...

Страница 12: ...except time setting can be reset to the factory settings Press Choose Function button until displays on the screen Press Confirm button all of parameters will be reset to factory settings 3 15 Manual...

Страница 13: ...ar system Check the pipeline and exhaust the air 6 Pump works but system doesn t have temperature difference meanwhile auxiliary heating function starts up Frost protection function is activated signa...

Отзывы: