2

 

Product information 

2.1

 

System description 

The solar collector pump (P1) is activated as soon as the temperature difference between the collector array (T1) 

and  the  storage  tank  (T2)  is  reached.  If  the  temperature  difference  between  the  collector  array  (T1)  and  storage 

tank  (T2)  drops  below  the  switch-off  temperature  difference,  or  the  storage  tank  (T3)  reaches  the  maximum 

storage temperature, the solar pump (P1) will be switched off. 

T3  is  used  to  measure  the  temperature  of  the  top  part  of  storage  tank.  If  the  turning-on  condition  for  auxiliary 

heating is filled, the auxiliary heating will be activated. 

 

 

1 collector array --- 1 storage tank 

 

T1: Temperature sensor for collector array 

T2: Temperature sensor in bottom part of storage tank 

T3: Temperature sensor in top part of storage tank 

P1: Solar collector pump 

P2: Solar circulation pump 

 

Danger:

  If  there  is  only  one  temperature  sensor  in  water  storage  tank  (usually  in  bottom  part  T2),  it  is 

possible,  that  the  auxiliary  heating  function  will  not  be  activated  or  deactivated  at  a  right  time,  because 

the  water  temperature  in  top  part  of  the  tank  (T3)  cannot  be  measured.  In  this  case,  if  you  still  want  to  use 

auxiliary heating function, control program will automatically take the signal from bottom temperature sensor (T2) 

instead of T3. However, water in top part of tank might often be overheated. It may cause damages to material and 

persons. So it is highly recommended not to use auxiliary heating in such a case. 

Note: 

To lock this function, please press 

Choose Function

 button until the signal 

 appears on the 

screen (see details in 3.5 Forbid/Permit using auxiliary heating). 

 

 

 

Содержание SP226

Страница 1: ......

Страница 2: ...operation is no longer possible please immediately take the device out of operation Without lightning rod please don t use this device during a thunderstorm 1 3 Liability waiver Improper installation...

Страница 3: ...or in bottom part of storage tank T3 Temperature sensor in top part of storage tank P1 Solar collector pump P2 Solar circulation pump Danger If there is only one temperature sensor in water storage ta...

Страница 4: ...Pump speed regulation 4 WILO pump 5 Input connector 6 Security valve 7 Expansion vessel connector 8 Output connector 9 Mounting point 2 2 2 Installation description SP116 should be installed in retur...

Страница 5: ...System working pressure 8 bar Safety valve response pressure 6 bar Ambient temperature 0 50 Input signals T1 T3 top part of water tank bottom part of water tank solar collector Output signals 3 auxili...

Страница 6: ...size 450mm 310mm 150mm Max own consumption 3W Range of temperature measuring NTC10K 0 99 PT1000 0 199 Accuracy of temperature measuring 1 Power of pumps solar collector pump P1 and circulation pump P...

Страница 7: ...on Setting three time periods Tank temperature As turning on off temperature value for auxiliary heating Solar system indication For SP116 SP226 only 1 system available Frost protection signal Overhea...

Страница 8: ...e Press Confirm button to save the setting press Cancel button to cancel the setting 3 2 Temperature difference circulation function The solar control program works on the principle of temperature dif...

Страница 9: ...time period Perform like above steps the other two time periods can be set Note If you want to shut off one of the three time periods you can set a same value for both start time and end time e g you...

Страница 10: ...ating Press Choose Function button until displays on the screen Press Confirm button to save the setting and forbid auxiliary heating Press Choose Function button until displays on the screen Press Ca...

Страница 11: ...the screen Press button to adjust the maximum collector temperature Default value 115 adjustable range 100 130 Press Confirm button to confirm the setting press Cancel button to quit this function 3 1...

Страница 12: ...except time setting can be reset to the factory settings Press Choose Function button until displays on the screen Press Confirm button all of parameters will be reset to factory settings 3 15 Manual...

Страница 13: ...ar system Check the pipeline and exhaust the air 6 Pump works but system doesn t have temperature difference meanwhile auxiliary heating function starts up Frost protection function is activated signa...