User

s Manual 

SP226 

10 

3.8

 

Frost protection 

In  winter,  when  the  temperature  of  collector  drops  below  the  preprogrammed  starting  temperature  of  frost 

protection (default  value 5

), solar pump P1 starts working.  When collector temperature exceeds the switch-off 

temperature  of  frost  protection,  pump  P1  stops  working  and  the 

system exits frost protection.   

ì

 

Press 

Choose Function

, until 

 displays on the screen. 

ì

 

Press 

“ ”“

  button  to  adjust  the  temperature  of  frost 

protection. Setting range: 3

10

ì

 

Press 

Confirm

 button to  confirm the setting, press 

Cancel

 

button to deactivate this function. 

 

3.9

 

High temperature protection of solar system 

When  collector  temperature  reaches  115

,  and  meanwhile  the  storage  tank  doesn

t  reach  the  max.  tank 

temperature, the high temperature protection function of solar system will be activated.

 

ì

 

Press 

Choose Function

, until 

  displays on the screen. 

ì

 

Press 

”“

  button  to  adjust  the  maximum  collector 

temperature.  Default  value:  115

, a

djustable  range:  100

130

ì

 

Press 

Confirm

 button to  confirm the setting, press 

Cancel

 

button to quit this function. 

 

3.10

 

Holiday function 

If  you  intend  to  be  absent  for  an  extended  period  (holiday),  or  hot  water  is  not  required  for  an  extended  period, 

you  can activate the  holiday  function. This  function is activated nightly to recool the storage  tank and to prevent 

high thermal loads of the solar system due to completely heated storage tank. 

 

ì

 

Press 

Choose  Function

, until 

 displays  on the screen, 

it indicates that the function is active.   

ì

 

Press 

Confirm

 button to confirm this setting. Press 

Cancel

 

button to deactivate this function. 

 

Note:

 When using holiday function, system will lock auxiliary heating automatically. 

 

3.11

 

Anti-legionella protection 

To safeguard the water hygiene, solar system will  monitor the storage tank temperature. If  the temperature  never 

reaches 70

  in every 7 days, auxiliary heating will be activated automatically and heats the tank water to 70

 

Содержание SP226

Страница 1: ......

Страница 2: ...operation is no longer possible please immediately take the device out of operation Without lightning rod please don t use this device during a thunderstorm 1 3 Liability waiver Improper installation...

Страница 3: ...or in bottom part of storage tank T3 Temperature sensor in top part of storage tank P1 Solar collector pump P2 Solar circulation pump Danger If there is only one temperature sensor in water storage ta...

Страница 4: ...Pump speed regulation 4 WILO pump 5 Input connector 6 Security valve 7 Expansion vessel connector 8 Output connector 9 Mounting point 2 2 2 Installation description SP116 should be installed in retur...

Страница 5: ...System working pressure 8 bar Safety valve response pressure 6 bar Ambient temperature 0 50 Input signals T1 T3 top part of water tank bottom part of water tank solar collector Output signals 3 auxili...

Страница 6: ...size 450mm 310mm 150mm Max own consumption 3W Range of temperature measuring NTC10K 0 99 PT1000 0 199 Accuracy of temperature measuring 1 Power of pumps solar collector pump P1 and circulation pump P...

Страница 7: ...on Setting three time periods Tank temperature As turning on off temperature value for auxiliary heating Solar system indication For SP116 SP226 only 1 system available Frost protection signal Overhea...

Страница 8: ...e Press Confirm button to save the setting press Cancel button to cancel the setting 3 2 Temperature difference circulation function The solar control program works on the principle of temperature dif...

Страница 9: ...time period Perform like above steps the other two time periods can be set Note If you want to shut off one of the three time periods you can set a same value for both start time and end time e g you...

Страница 10: ...ating Press Choose Function button until displays on the screen Press Confirm button to save the setting and forbid auxiliary heating Press Choose Function button until displays on the screen Press Ca...

Страница 11: ...the screen Press button to adjust the maximum collector temperature Default value 115 adjustable range 100 130 Press Confirm button to confirm the setting press Cancel button to quit this function 3 1...

Страница 12: ...except time setting can be reset to the factory settings Press Choose Function button until displays on the screen Press Confirm button all of parameters will be reset to factory settings 3 15 Manual...

Страница 13: ...ar system Check the pipeline and exhaust the air 6 Pump works but system doesn t have temperature difference meanwhile auxiliary heating function starts up Frost protection function is activated signa...

Отзывы: