UFR1001E
12420-0701-08
Page
6 / 45
www.ziehl.de
11
Sealable LED
Press for > 2 s
Lock / Unlock
LED red
Settings and simulation mode are locked,
While attempting to set,
8
8
is displayed for 3s
LED green
Setting and simulation enabled
4.
Detailed description
4.1 Description of the connections
Connection
Description
A1 and A2
Rated control supply voltage Us, see Technical Data
11, 12, 14; 21, 22, 24
Relay K1 and K2
E1 E2
Enable Input
Volt-free contact
8
8
8
8
, no function
8
8
8
8
, E1-E2 closed: Vector shift active but not evaluated,
monitoring of feedback contacts off for use with generator (mains
synchronization)
8
8
8
8
, E1-E2 closed: K1 and K2 off (standby), vector shift
off
8
8
8
8
, E1-E2 closed: Feedback contacts no evaluated,
vector shift off, when using with generator (mains synchronization)
Y0, Y1, Y2
Inputs, feedback contacts
Volt-free n/o or n/c contact, self-learning when switching on
Set value > turn-on time section switch under
8
8
8
8
/ can
switch-off if not connected or if external devices/switches can activate
the section switch (
8
8
)
I1
Supply voltage for digital outputs, max. 27 V DC
Digital output over-/under voltage/-frequency, Q3 + Q4 = ROCOF
Q5
Digital output error, in Programs with >> and << additionally the 2nd
threshold value
L1, L2, L3, N
Phase L1, L2, L3 and neutral conductor
4.2 Functional characteristics
Functional characteristics Explanation
VSR display value
The highest measured value is always displayed. The display value is reset to 0
by deleting the max. value and when resetting into the go (good) state.
Delay Enable On time
Runs down when starting the unit and after opening the enable input; during this
time there is no evaluation of the vector shift
Reset time
When a reset time
8
8
is running, it is always counted down in the display
(shortest one first)
Reset
Use the Reset key or interrupt the control voltage for > 2 s (comply with reset
delay)
Display mode
8
8
After the last measurement it switches into the scan mode; this is indicated by
the display
8
8
.
All measurements will now be displayed cyclically for the time set in
8
8
.
MIN / MAX values
All min and max values are saved zero-voltage maintained (non-volatile).
Содержание UFR1001E
Страница 31: ...UFR1001E 12420 0701 08 Page 31 45 www ziehl de 14 Certificate of conformity VDE AR N 4105 ...
Страница 32: ...UFR1001E 12420 0701 08 Page 32 45 www ziehl de ...
Страница 33: ...UFR1001E 12420 0701 08 Page 33 45 www ziehl de 15 Certificate of conformity bdew 2008 2013 ...
Страница 34: ...UFR1001E 12420 0701 08 Page 34 45 www ziehl de ...
Страница 35: ...UFR1001E 12420 0701 08 Page 35 45 www ziehl de ...
Страница 36: ...UFR1001E 12420 0701 08 Page 36 45 www ziehl de ...
Страница 37: ...UFR1001E 12420 0701 08 Page 37 45 www ziehl de ...
Страница 38: ...UFR1001E 12420 0701 08 Page 38 45 www ziehl de ...
Страница 39: ...UFR1001E 12420 0701 08 Page 39 45 www ziehl de ...
Страница 40: ...UFR1001E 12420 0701 08 Page 40 45 www ziehl de 16 Certificate of conformity ÖVE ÖNORM E 8001 4 712 Pr 10 ...
Страница 41: ...UFR1001E 12420 0701 08 Page 41 45 www ziehl de 17 Certificate of conformity GB G59 3 Pr 20 21 ...
Страница 42: ...UFR1001E 12420 0701 08 Page 42 45 www ziehl de 18 Certificate of conformity GB G83 2 Pr 22 23 ...
Страница 43: ...UFR1001E 12420 0701 08 Page 43 45 www ziehl de 19 Certificate of conformity DIN V VDE V 0126 1 1 GB ...
Страница 44: ...UFR1001E 12420 0701 08 Page 44 45 www ziehl de 20 Certificate of conformity DIN V VDE V 0126 1 1 Fr ...