UFR1001E
12420-0701-08
Page
29 / 45
www.ziehl.de
12.
Troubleshooting and measures
Error
Cause
Remedy
8
8
or
8
8
appears in the
display
Measurement is
above/below range
Measured voltage, frequency or the vector
surge is too large or too small; comply with
measurement range
8
8
appears in
the display
Tolerance error, internal
measurement value
deviation of both channels
Perform a reset interrupt control voltage
for >5s
*
8
8
appears in
the display
Error internal interface
8
8
appears in
the display
Communication error,
internal interface
8
8
also appears
in the display after 2
automatic
reconnection
attempts, LED K1
and / or K2
illuminated
Feedback contacts
connected
Feedback contacts not connected
Set -
8
8
8
8
8
8
Feedback contacts not connected
- Check for correct connection
- Set turn-on time of section switch under
8
8
- Perform a reset interrupt control voltage
for >5s
8
8
appears in
the display
Hysteresis error
Upper threshold value must be higher than
the lower threshold value, check the
threshold values
8
8
appears in
the display
Parameter error
*
A time expires in the
display
Always when an OFF-delay
time
8
8
is running, it is
counted down in the
display (shortest one first)
Wait until the time has expired (depending
on the setting, several times may elapse
one after the other)
Device cannot be
configured / only the
limits can be
configured
Code lock / Sealing
activated
If there are any problems with the code lock
(pin forgotten), the lock can be switched off
and the pin can be reset to 504 by keeping
the Set key pressed while switching on the
mains until
8
8
8
8
appears in
the display.
Implausible voltage
values
Pr selected with N, but N
not connected
Select Pr without N or connect N
8
8
appears in
the display
Seal is active
See Sealing
8
8
appears in
the display
Code lock is active
8
8
appears in
the display
Standby mode, E1-E2
closed
Check parameter
8
8
8
8
and LED Q3
(f>) is on, reading in
good range
hysteresis for
8
8
incorrectly
Check hysteresis for reset point
50,05 Hz
*
If the error cannot be patched by a reset, send back to factory for repair.
Содержание UFR1001E
Страница 31: ...UFR1001E 12420 0701 08 Page 31 45 www ziehl de 14 Certificate of conformity VDE AR N 4105 ...
Страница 32: ...UFR1001E 12420 0701 08 Page 32 45 www ziehl de ...
Страница 33: ...UFR1001E 12420 0701 08 Page 33 45 www ziehl de 15 Certificate of conformity bdew 2008 2013 ...
Страница 34: ...UFR1001E 12420 0701 08 Page 34 45 www ziehl de ...
Страница 35: ...UFR1001E 12420 0701 08 Page 35 45 www ziehl de ...
Страница 36: ...UFR1001E 12420 0701 08 Page 36 45 www ziehl de ...
Страница 37: ...UFR1001E 12420 0701 08 Page 37 45 www ziehl de ...
Страница 38: ...UFR1001E 12420 0701 08 Page 38 45 www ziehl de ...
Страница 39: ...UFR1001E 12420 0701 08 Page 39 45 www ziehl de ...
Страница 40: ...UFR1001E 12420 0701 08 Page 40 45 www ziehl de 16 Certificate of conformity ÖVE ÖNORM E 8001 4 712 Pr 10 ...
Страница 41: ...UFR1001E 12420 0701 08 Page 41 45 www ziehl de 17 Certificate of conformity GB G59 3 Pr 20 21 ...
Страница 42: ...UFR1001E 12420 0701 08 Page 42 45 www ziehl de 18 Certificate of conformity GB G83 2 Pr 22 23 ...
Страница 43: ...UFR1001E 12420 0701 08 Page 43 45 www ziehl de 19 Certificate of conformity DIN V VDE V 0126 1 1 GB ...
Страница 44: ...UFR1001E 12420 0701 08 Page 44 45 www ziehl de 20 Certificate of conformity DIN V VDE V 0126 1 1 Fr ...