10.3 Code lock / code reset
The device can be protected with the code lock against unauthorized changes to the device (via joystick
button) (
menu -> settings -> code lock
). A pin code is used for this (
factory setting: 504
).
Reset pin code / disable code lock,
On the device:
•
Switch off the supply voltage
•
Push the joystick button up (and keep it pressed)
•
Switch on the supply voltage (keep the button pressed)
•
After approx. 4s, the reset menu appears, select the code lock and push the button to the
right
•
Code lock is off, pin code is reset to = 504
Via web interface:
•
Open the page system, deactivate code lock and save it with a push on the save button.
10.4 Description of the display pages
10.4.1 Measured value page (1/3)
- Measurements of all 6 sensors at a glance
- Sensor names (7 characters) can be set via web interface
- If a measured value triggers an alarm, it receives a coloured
background
- Pt100, Pt1000 sensors can be recognized by the unit
„°C“
- PTC thermistors can be recognized by the unit
„kΩ“
- Is one of the following signs used instead of the measured value:
o
„---“ is displayed, the sensor is deactivated
o
„>>>“ or „<<<“ is displayed, the current measured value is larger
or smaller than the measuring range
- Joystick button
o
Push short upwards => display page for min. / max. values
o
In the case of a backshift ready locked alarm, push the button 2s
upwards to reset the alarm.
10.4.2 Sensor to alarm assignment (2/3)
- Tabular assignment of the sensors to the alarms
X (white)=> sensor acts on alarm,
X (orange) => sensor has exceeded limit,
R (red) => sensor triggered alarm by the ROCOT function,
2 (orange) => two sensors triggered alarm by the function
„2 of x“
E (red) => sensor error (short circuit or sensor break)
- Alarm state of the relays can be seen
(Kx (white) => relay dropped, Kx (yellow) => relay energized)
- Set alarm limit
Info
Firmware version
Display of the current installed firmware
version
Serial number
Display the serial number
Operating hours
Operating hours of the device
Comment
Comment of the customer (setting via web
browser only)
Counter
alarm counter
Alarm counter for each alarm
last 20 alarms
statistic 1
Sensor statistic (resettable)
statistic complete
Sensor statistic (not resettable)
reset
Deleting the alarm counter and sensor
statistic 1