10.2  Description of the parameters 

menu 

parameter 

explanation 

setting 

program 

Preset programs for 
the areas: 
1. Trafo-safety, 
2. Motor-safety, 
3. others… 

Load predefined programs for fast and 
comfortable setting of the TR660IP 

sensors 
1T … 6T 

type 

Setting the respectively connected sensor 
type 

off, 

Pt100, 

Pt1000, 

PTC 

Line-resistance 

Line-resistance between device and 
sensor. Setting in ohms, or as 3-wire with 
automatic compensation of cable 
resistance. 

3- wire, 

0,0 … 100,0 Ω 

Alarm 
K1 … K7 

Sensors 

Assignment of which sensors acts on this 
alarm. 

1T … 6T 

2 of x 

If this function is on, 2 of the assigned 
sensors must meet the alarm conditions to 
trigger the alarm. 

Function can only be activated if 2 
sensors are assigned to this alarm.

 

on, 

off 

alarm on 

Temperature value at which the alarm is 
triggered. 
If a PTC is assigned to the alarm, fixed 
switch-off values for PTC thermistors are 
used. 

-

199,9 … 800,0 °C 

alarm off 

Temperature value at which the alarm is 
switches back. 
If a PTC is assigned to the alarm, fixed 
reset values for PTC thermistors are used. 

-

199,9 … 800,0 °C 

Delay alarm on 

Delay time between reaching the alarm on 
value and switching the relay. 

00:00 … 59:59 

mm:ss 

Delay alarm off 

Delay time between reaching the alarm off 
value and switching the relay. 

00:00 … 59:59 

mm:ss 

Relay function 

Function how the relay should behave in 
case of an alarm 

On at alarm, 

off at alarm, 

manually on, 

manually off 

Alarm locked 

If the function is activated, the alarm must 
be switched back manually on the device, 
via the web browser or via an external 
switch on Y1 + Y2. 

on, 

off 

Sensor error 

Selection of sensors for which the relay 
issues a fault message in the event of a 
sensor error. 

1T … 6T 

Device error 

Activation to report a device error with this 
relay. 

on, 

off 

ROCOT 

Function for switching off at rapid 
temperature rise. (

see ROCOT

off, 

°C/s, 

time 

ROCOT [°C/s] 

Parameterization of the line slope 
between two measured values. 

0,1 … 10,0 °C/s 

ROCOT [Zeit] 

Setting the calculation time for the 
ROCOT time shutdown 

00:10 … 20:00 

mm:ss 

Cyclic test 
K1 … K7 

Cyclic test 

Activation of the cyclic relay test 

on, 

off 

Delay on 

Duration after which time the cyclic test is 
repeated 

00-

01 … 90-00 

dd-hh 

Содержание TR660IP

Страница 1: ...and Plant Protection Operating Manual TR660IP updated 2022 11 29 sm from Firmware 0 06 For more information and help about this product please scan the QR Code or choose the following link TR660IP Ope...

Страница 2: ...de reset 13 10 4 Description of the display pages 13 10 4 1 Measured value page 1 3 13 10 4 2 Sensor to alarm assignment 2 3 13 10 4 3 Info page 3 3 14 10 5 Special functions 14 10 5 1 2 of x 14 10 5...

Страница 3: ...er 19 13 Error search 19 14 Disposal 20 15 Technical data 21 16 Housing V8 23 17 Factory settings of the programs 24 1 General Notes Compliance with the following instructions is mandatory to ensure t...

Страница 4: ...set programs cover most applications The required program can easily be selected via the menu push button down 2s programs Alternatively the program can be selected via the web server page configurati...

Страница 5: ...C For each alarm sensor fault and device fault can be parameterized Free adjustable delay times for Alarm on and Alarm off 2 of x o The function 2 of x triggers the alarm only if at least 2 of the sen...

Страница 6: ...6 Connecting diagram 6 1 TR660IP Analog 6 2 TR660IP RS485 CAUTION For the last device in the RS485 bus the bridges 1 must be screwed in from D1 to D1 and from D0 to D0 Wire bridges are not included 6...

Страница 7: ...h installation start and use and who have appropriate qualification corresponding to their function They must observe the contents of the instructions manual the information which are written on the e...

Страница 8: ...are required for the correct operation of the alarm counter If the date has not been set the alarm counter will show the year 1970 After these settings have been made the monitoring starts The setting...

Страница 9: ...fo save 3x Pt100 same settings as Pr2 TR250 1T Pt100 2T Pt100 3T Pt100 4T off 5T off 6T off K1 fan with cyclic test K2 pre alarm K3 tripping K4 sensor device error 1 01 Trafo save 1x Pt100 2x PTC same...

Страница 10: ...01 other 6x PTC Single allocation 1T PTC 2T PTC 3T PTC 4T PTC 5T PTC 6T PTC K1 sensor 1T K2 sensor 2T K3 sensor 3T K4 sensor 4T K5 sensor 5T K6 sensor 6T K7 sensor device error 3 02 other 6x Pt100 1T...

Страница 11: ...ack If a PTC is assigned to the alarm fixed reset values for PTC thermistors are used 199 9 800 0 C Delay alarm on Delay time between reaching the alarm on value and switching the relay 00 00 59 59 mm...

Страница 12: ...0 C Fullscale 199 9 800 0 C RS485 Modbus TR660IP RS485 only BUS address Bus address of the TR660IP 001 247 Baud rate Communication speed 4800 9600 19200 57600 Parity Parity bit No odd even Stop Bits...

Страница 13: ...k Is one of the following signs used instead of the measured value o is displayed the sensor is deactivated o or is displayed the current measured value is larger or smaller than the measuring range J...

Страница 14: ...om the actual and the previous average 10 5 2 1 Slope C s If the calculated slope is greater than the set value the alarm becomes active 10 5 2 2 Time s Alarm if the set limit value would be reached a...

Страница 15: ...nloaded from the homepage www ziehl com Then the update file can be selected under system manual installation select firmware and carried out via the button manual update installation 10 8 Alarm count...

Страница 16: ...nt version and can be updated if necessary o new programs can be installed on the TR660IP Configuration recent changes to the device are saved with the date time and the username see user management o...

Страница 17: ...ure ranges 10 C each e g 0 0 9 9 C from 0 0 up to 199 9 C In addition there is an area for 0 0 C and one for 200 0 C This statistic is available twic resettable via manual reset or by program change a...

Страница 18: ...protection see Factory settings of the programs Firmware update TR660IP o Update notification message if update is available o Firmware status if necessary the firmware update can carry out via the up...

Страница 19: ...urement status values when changing the status of one or more alarms 12 7 Counter Alarm counter o Recording of the last 20 alarms per relay with time stamp and alarm cause Temperature statistics o Rec...

Страница 20: ...hed off and the code can be reset to 504 by keeping the button pressed up approx 5s when switching on the supply voltage Now the code lock can be reset No access via ethernet DHCP is on but no IP addr...

Страница 21: ...240 V UL electrical ratings 250 V ac 3 A general use 240 V ac 1 4 hp 2 9 FLA 120 V ac 1 10 hp 3 0 FLA C300 External inputs approx DC 18 V 3 5 mA Reset input Y1 Y2 Reset of locked alarms dynamic Senso...

Страница 22: ...Ethernet interface RJ45 connection Speed 10 100 Mbit s Real time clock Power reserve 11 days at 25 C Time deviation 3 ppm EMC tests EN 61326 1 industrial environment EMC emission EN 61326 1 CISPR 11...

Страница 23: ...ening on 35 mm mounting rail acc EN 60 715 or with M4 screwed attachment additional bar not included in the scope of delivery Weight app 370 g Subject to technical changes 16 Housing V8 Dimension in m...

Страница 24: ...ine resistance 3 wire 3 wire Sensor 3T Sensor name winding 3 winding 123 winding 3 Type Pt100 PTC Pt100 Line resistance 3 wire 3 wire Sensor 4T Sensor name core Type off off Pt100 Line resistance 3 wi...

Страница 25: ...3 Alarm name tripping tripping Tripping winding Sensors 1T 2T 3T 3T 1T 2T 3T 2 of X off off off Alarm on C 155 0 C PTC 150 0 C Alarm off C 150 0 C PTC 145 0 C Delay alarm on mm ss 00 00 00 00 00 00 De...

Страница 26: ...2 Cyclic test on off off off off Delay on DD hh Time on hh mm Cycl test K3 Cyclic test on off off off off Delay on DD hh Time on hh mm Cycl Test K4 Cyclic test on off off off off Delay on DD hh Time o...

Страница 27: ...inding 3 winding 123 core Type Pt100 PTC PTC Line resistance 3 wire Sensor 4T Sensor name core core Type Pt100 PTC off Line resistance 3 wire 3 wire 3 wire Sensor 5T Sensor name Type off off off Line...

Страница 28: ...n mm ss 00 00 00 00 00 00 Delay alarm off mm ss 00 00 00 00 00 00 Relay function on at alarm off at alarm on at alarm Alarm locked off off off Sensor error 1T 2T 3T 4T Device error off on off ROCOT of...

Страница 29: ...off at alarm on at alarm off at alarm Alarm locked off off off Sensor error 1T 2T 3T 4T 1T 2T 3T Device error on off on ROCOT off off off ROCOT temperature C s ROCOT change mm ss Cyclic test Cycl test...

Страница 30: ...4x Pt100 Fan control pre alarm Pre alarm tripping winding my 3x windings tripping winding tripping core main under Parameter data 1x core tripping core Function monitoring menu menu menu Pr1 03 Pr1 0...

Страница 31: ...00 Pt100 Line resistance 3 wire 3 wire Sensor 4T Sensor name Sensor 4T Type off off Pt100 Line resistance 3 wire 3 wire 3 wire Sensor 5T Sensor name Sensor 5T Type off off Pt100 Line resistance 3 wire...

Страница 32: ...Delay alarm off mm ss 00 00 00 00 00 00 Relay function on at alarm off at alarm on at alarm Alarm locked off off off Sensor error Device error off off off ROCOT off off off ROCOT temperature C s ROCOT...

Страница 33: ...alarm on at alarm Alarm locked off off off Sensor error 1T 2T 3T Device error on off off ROCOT off off off ROCOT temperature C s ROCOT change mm ss Cyclic test Cycl test K1 Cyclic test on off on off...

Страница 34: ...fe Other Fan control pre alarm 3x Pt100 6x Pt100 my tripping winding Individual assignment main under Parameter data Function monitoring menu menu menu Pr1 06 Pr2 00 Pr3 00 Simulation Relay Sensor Inf...

Страница 35: ...e resistance 0 0 3 wire Sensor 4T Sensor name PTC 4T Sensor 4T Type PTC Pt100 Line resistance 0 0 3 wire Sensor 5T Sensor name PTC 5T Sensor 5T Type PTC Pt100 Line resistance 0 0 3 wire Sensor 6T Sens...

Страница 36: ...perature C s ROCOT change mm ss Alarm K3 Alarm name PTC 3T Sensor 4T 5T Sensors 3T 4T 5T 2 of X off off Alarm on C PTC 80 0 Alarm off C PTC 77 0 Delay alarm on mm ss 00 00 00 00 Delay alarm off mm ss...

Страница 37: ...y on DD hh 00 01 07 00 Time on hh mm 00 33 00 00 Cycl test K3 Cyclic test on off off off Delay on DD hh 00 01 07 00 Time on hh mm 00 33 00 00 Cycl Test K4 Cyclic test on off off off Delay on DD hh 00...

Отзывы: