TR660IP
12780-0702-02
Page
12 / 37
www.ziehl.de
Time on
Duration for which the test is active
00:01 … 23:59
hh:mm
Analog-
output
(TR660IP
Analog only)
OUT 1 voltage
range
0 … 10V
2 … 10V
Sensors that act on this analogue output
1T … 6T
Temperature output
Min. temperature,
max. temperature
Zero
-
199,9 … 800,0 °C
Fullscale
-
199,9 … 800,0 °C
OUT 1 current
range
0 … 20mA
4 … 20mA
Sensors that act on this analogue output
1T … 6T
Temperature output
Min. temperature,
max. temperature
Zero
-
199,9 … 800,0 °C
Fullscale
-
199,9 … 800,0 °C
OUT 2 voltage
range
0 … 10V
2 … 10V
Sensors that act on this analogue output
1T … 6T
Temperature output
Min. temperature,
max. temperature
Zero
-
199,9 … 800,0 °C
Fullscale
-
199,9 … 800,0 °C
OUT 2 current
range
0 … 20mA
4 … 20mA
Sensors that act on this analogue output
1T … 6T
Temperature output
Min. temperature,
max. temperature
Zero
-
199,9 … 800,0 °C
Fullscale
-
199,9 … 800,0 °C
RS485
–
Modbus
(TR660IP
RS485 only)
BUS address
Bus address of the TR660IP
001 … 247
Baud rate
Communication speed
4800,
9600,
19200,
57600
Parity
Parity bit
No, odd, even
Stop Bits
Number of stop bits
1 … 2
Network
DHCP
Dynamic Host Configuration Protocol
(DHCP)
The device gets its IP address from the
server
on,
off
IP-address
Manual setting of the IP address in the
network
Subnet mask
Manual setting of the subnet mask
Settings
Language
Setting of the language of the display
German,
English
Date
Setting the current date
time
Setting the current time
Display interval
Duration to update the display
0,1 … 2,0 s
Brightness
Display brightness
20 … 100%
Dimming time
Duration until the display brightness is
reduced
00:10 … 59:59
mm:ss
Factory settings
Load the parameters of the current active
program
no,
yes
Code protection
Code protection so that the settings can
be protected
Factory setting: 504
on,
off
Simulation
Sensors
Simulation of a single sensor value
Relay
Simulation of a single relay state