background image

TR400  

12360-0706-05

  

Page

 

6 / 12 

www.ziehl.de 

  

Assembly 

  mount on 35 mm mounting rail according to EN 60715 

  wall-mount with 3 x screws M4 

  connecting wires refer to the wiring diagram to prevent miss-operation and malfunction. 

 

A circuit-breaker or switch must be situated within easy reach of the  
unit and fused. Installation excess current protection should be ≤ 10 A.  

 
 

Putting into operation  

Remarks 

 

LEDs Alarm 

 

 

off:   

 

 

 

temperature below switching point 

 

on:   

 

 

 

temperature beyond switching point 

 

blinking 1x on 4x off:    

alarm-relay delay time t

ALARM

 is running 

blinking 4x on 1x off:  

alarm-relay delay time t

ALARM

 off is running  

 

blinking 1x on 1x off:    

relay locked, ready for reset 

Alarm-relay can be resetted with reset-push-button or external contact closed Y1, Y2. A closed contact 
or short circuit at terminals Y1-Y2 means no autoreset function.  

 

 

Functions of USB-Stick  

With the 2 functions 

 

 

„transfer configuration-file from TR400 to USB-Stick“  

 

„transfer configuration-file from USB-Stick to TR400“  

settings of a readily configured TR400 can be easily read-out and transferred to other TR400. 
 

The USB-Stick is necessary for configuration and for firmware-updates only.  
It may not stay plugged during normal operation. 

 
Select Mode „A“, then choose function with button „Alarm Select“:  

  Alarm LED 2 = transfer configuration-file from USB-Stick to TR400 

  Alarm LED 3 = transfer configuration-file from TR400 to USB-Stick 

  Alarm LED 4 = update of firmware  

Attention: As long as TR400 is reading from or writing on the USB-Stick, all relays are released and no 
values are measured 
The file system on the USB-Stick has to FAT or FAT32. The files must be located in the main directory 
(highest level) of the USB-Stick. 

Info’s and Downloa

www.ziehl.com

. 

File for configuration: „TR600.cfg“ /  file for firmware-update: „TR600.hex“ 
 

O

www.ziehl.com

 / downloads a parameterizing web site is available.  

With this help the following activities can be done easily: 
 

- create and change configuration-files 

 

- check downloaded configurations-files  

 

- documentation of configuration-files  

 
You will also find a update instruction and the latest firmware-version there. 

 

 

 

!

Содержание TR400

Страница 1: ...de www ziehl de Temperature Relays and MINIKA Mains Monitoring Digital Panelmeters MINIPAN Switching Relays and Controls Measuring Transducers Grid and Plant Protection Operating Manual TR400 updated...

Страница 2: ...ts 1 Application and short description 3 2 Overview of functions 3 3 Connection plan 3 4 Display and operating elements 4 5 Function diagram 4 6 Important notes 5 7 Assembly 6 8 Putting into operation...

Страница 3: ...rature monitoring wherever up to 4 different measuring points must be monitored simultaneously motors and generators with simultaneous monitoring of bearings and coolant transformers with additional m...

Страница 4: ...sor 3 4x LED Alarm 4 Select buttons 5 Display 3 digits 6 Up button 7 Down button 8 Mode button 9 Set button 10 Display 1 digit Mode 11 Reset button 12 Terminal for USB Stick 4 Function diagram sensor...

Страница 5: ...sensors must be connected to the plug in terminals 1T1 1T2 1T3 etc To ensure proper operation this plug in terminals have gold plated contacts Do not use these plugs for other terminals The measuring...

Страница 6: ...tion file from USB Stick to TR400 settings of a readily configured TR400 can be easily read out and transferred to other TR400 The USB Stick is necessary for configuration and for firmware updates onl...

Страница 7: ...lue of the compensation line resistance RK must be calculated as follows RK n 1 x RL 2 RL line resistance of two wires n number of sensors Sensor Simulation At this menu item a sensor or sensor group...

Страница 8: ...nsor 4 4 4 20 mA 4 2 10 V Zero 199 800 C Store 0 C 0 mA FullScale 199 800 C Store 100 C 20 mA 8 Sensor Simulation sensor 1 4 199 800 C 9 Code safe off 500 safe 500 Code safe on 504 free on off on A US...

Страница 9: ...ruption of power supply ATTENTION There is a short alarm signal of K7 when switching on the supply voltage Sensor alarm relay K7 with operating function 1 NO contact picks up at any failure ATTENTION...

Страница 10: ...ance 1 of programmed span 1 C Relay Data K1 K4 and K7 5 x 1 change over contacts Switching voltage max AC 415 V Switching current max 5 A Switching capacity max 1250 VA resistive load max 120 W at DC...

Страница 11: ...150 Hz 5 g Galvanic insulation Test voltage Us Relays sensors USB analog output Reset input DC 3820 V Relays sensors USB analog output Reset input DC 3820 V No galvanic insulation sensors USB analog...

Страница 12: ...en f r unten position downward 7 Riegel bei Wandbefestigung mit Schrauben Riegelbohrung 4 2 mm for fixing to wall with screws 4 2 mm Sie finden diese und weitere Betriebsanleitungen soweit verf gbar a...

Отзывы: