background image

TR400  

12360-0706-05

  

Page

 

8 / 12 

www.ziehl.de 

  

Setup * 

Mode  Function 

 Alarm select 

 Sensor 

select 

 Display  

 SET 

 Factory Adjust 

Switching Point (°C) 

 

Relay 1…4  Sensor 1…4   -199°…800°C 

Store 

100 °C 

 

 

 

group *

1)

 

 

 

Alarm 1 = Sensor 1…3 

 

 

 

 

 

 

Alarm 2 = Sensor 1…3 

 

 

 

  

 

 

Alarm 3 = Sensor 4 

 

 

 

 

 

 

Alarm 4 = Sensor 4 

Hysteresis (K) 

 

Relay 1…4 

1 …99 K 

Store 

 3 K 

tALARM (s) 

 

Relay 1…4 

 - 

0,1 … 99,9 s 

Store 

 0,1 s 

tALARM off (s) 

 

Relay 1…4 

 - 

0 … 999 s 

Store 

 0 s 

autoreset - locked 

 

Relay 1…4 

 - 

0 = autoreset 

Store 

 0 = autoreset 

 

 

 

 

1 = locked 

 

 

Operating function 

 

Relay 1…4 

 - 

 

 

 

 

Max-NO contact 

Sensor alarm 

 



Store 

 

 

Max-NC contact 

 

 



 



 

 

Min-NO contact 

 

 



 

 

 

Min-NC contact 

 

 



 

 

Sensor connection 

sensor 1…4 

 

 

3-.L 

 

3-wire 

 

 

3-.L 

Store 

 

  

not connected 

 

 

n.c.

 *

3

 

 

 

 

2-

wire (Ω) 

 

 

0…99,9  

 

 

Analog out 

Out 1 = 1 

sensor 1…4  0 = 0…20 mA 

Store 

Out 1 = group 1+2+3 

 

 

Out 2 = 2 

group *

1)

 

*2)

  0 = 0…10 V 

 

Out 2 = sensor 4 

  

 

 

 

4 = 4…20 mA 

 

 

 

 

  

 

4 = 2…10 V 

 

 

  

Zero 

 -

199°…800°C 

Store 

0 °C = 0 mA 

  

FullScale 

 -

199°…800°C 

Store 

100 °C = 20 mA 

Sensor Simulation 

sensor 1…4   -199°…800°C 

 

Code safe = off 

500 (safe) 

  

500 

  

Code safe = on 

  

  

504 (free) 

on/off/on 

  

USB 

Config To TR 

= 2 

 

Start 

 

 

 

Config To USB 

= 3 

 

 

Start 

 

 

 

Firmware 

Update = 4 

 

 

(+ button Reset) ->  Start

 

* return within 30 s without any button pushed 

*

1)

 group: - sensor 1+2+3, - sensor 1+2+3+4, - sensor 1+2, - sensor 3+4 

*

2)

 When a group of sensors is selected, the warmest temperature makes the signal for the analog output. 

*

3

) not connected (no sensor connected)

 

 

 

 

Trouble shooting 

 

LED Sensor Error 

The LED sensor error indicates a failure at a sensor  and the sensor-LED blinks. The sensor alarm relay 
K7 has switched. Refer to operation  mode 5. Also see analog output. 
 

 

Display 
EEE

   

sensor interruption or over-range   

-EE

    

sensor short circuit or under 

–range 

 

 

Analog output 0 mA/0 V 

If sensor failure short circuit or sensor interruption is detected the output current is 0 mA and the output 
voltage 0 V. 

 

Содержание TR400

Страница 1: ...de www ziehl de Temperature Relays and MINIKA Mains Monitoring Digital Panelmeters MINIPAN Switching Relays and Controls Measuring Transducers Grid and Plant Protection Operating Manual TR400 updated...

Страница 2: ...ts 1 Application and short description 3 2 Overview of functions 3 3 Connection plan 3 4 Display and operating elements 4 5 Function diagram 4 6 Important notes 5 7 Assembly 6 8 Putting into operation...

Страница 3: ...rature monitoring wherever up to 4 different measuring points must be monitored simultaneously motors and generators with simultaneous monitoring of bearings and coolant transformers with additional m...

Страница 4: ...sor 3 4x LED Alarm 4 Select buttons 5 Display 3 digits 6 Up button 7 Down button 8 Mode button 9 Set button 10 Display 1 digit Mode 11 Reset button 12 Terminal for USB Stick 4 Function diagram sensor...

Страница 5: ...sensors must be connected to the plug in terminals 1T1 1T2 1T3 etc To ensure proper operation this plug in terminals have gold plated contacts Do not use these plugs for other terminals The measuring...

Страница 6: ...tion file from USB Stick to TR400 settings of a readily configured TR400 can be easily read out and transferred to other TR400 The USB Stick is necessary for configuration and for firmware updates onl...

Страница 7: ...lue of the compensation line resistance RK must be calculated as follows RK n 1 x RL 2 RL line resistance of two wires n number of sensors Sensor Simulation At this menu item a sensor or sensor group...

Страница 8: ...nsor 4 4 4 20 mA 4 2 10 V Zero 199 800 C Store 0 C 0 mA FullScale 199 800 C Store 100 C 20 mA 8 Sensor Simulation sensor 1 4 199 800 C 9 Code safe off 500 safe 500 Code safe on 504 free on off on A US...

Страница 9: ...ruption of power supply ATTENTION There is a short alarm signal of K7 when switching on the supply voltage Sensor alarm relay K7 with operating function 1 NO contact picks up at any failure ATTENTION...

Страница 10: ...ance 1 of programmed span 1 C Relay Data K1 K4 and K7 5 x 1 change over contacts Switching voltage max AC 415 V Switching current max 5 A Switching capacity max 1250 VA resistive load max 120 W at DC...

Страница 11: ...150 Hz 5 g Galvanic insulation Test voltage Us Relays sensors USB analog output Reset input DC 3820 V Relays sensors USB analog output Reset input DC 3820 V No galvanic insulation sensors USB analog...

Страница 12: ...en f r unten position downward 7 Riegel bei Wandbefestigung mit Schrauben Riegelbohrung 4 2 mm for fixing to wall with screws 4 2 mm Sie finden diese und weitere Betriebsanleitungen soweit verf gbar a...

Отзывы: