10.8 Configuring sensors
Adjustment process:
•
Select the menu item with the Up/Down key until …
Display
8
SEN.
8
•
Press the Set key
Display
8
S 1
8
/
8
3-L
8
(Sensor 1 / Connection type) flash alternately
•
Use the Up and Down buttons to set the connection type or line resistance.
Sensor not connected: Select
8
nc
8
3-wire connection: Select
8
3-L
8
2-wire connection:
8
0.00
8
Perform a line compensation and adjust the line resistance
•
Press the Set key
Display
8
S 2
8
/
8
3-L
8
(Sensor 2 / Connection type) flash alternately
•
Configure all 12 sensors in this manner.
10.9
Configuring the relay
Adjustment process:
•
Select the menu item with the Up/Down key until…
Display
8
rel.
8
(Relay function)
•
Press the Set key
Display
8
rel
8
/
8
r
8
(Relay function / Zero signal current) flash alternately
•
Use the Up and Down keys to select the relay function
•
Press the Set key (exits the configuration mode)
Display
8
rel.
8
(Relay function)
10.10
Configuring the Ethernet interface
Adjustment process:
•
Select the menu item with the Up/Down key until …
Display
8
IP .
8
(Bus)
•
Press the Set key
Display
8
IP1
8
/
8
192
8
(IP address 1st block / 192) flash alternately
•
Set the desired address for 1st block of the IP using the Up and Down keys
•
Press the Set key
Display
8
IP1
8
/
8
168
8
(IP address 2nd block / 168) flash alternately
•
Set the desired address for 2nd block of the IP using the Up and Down keys
•
Press the Set key
Display
8
IP3
8
/
8
1
8
(IP address 3rd block / 1) flash alternately
•
Set the desired address for 3rd block of the IP using the Up and Down keys
•
Press the Set key
Display
8
IP4
8
/
8
100
8
(IP address 4th block / 50) flash alternately
•
Set the desired address for 4th block of the IP using the Up and Down keys
•
Press the Set key
Display
8
IP .
8
(IP address)
•
Press Down key