TR640IP 

12760-0702-00

 

Page

 

14 / 18 

www.ziehl.de 

  

11 

Error search 

Error 

Root cause 

Help 

Relay always switches after a 
fixed time interval 

Cyclic relay test is activated 

Deactivate cyclic relay test  

Relay does not turn on or off 
when an alarm is reached 

Relay has been parameterized to 
“manual on” or “manual off”. The 
display shows below the 
respective relay an “M”. 

Change relay setting 
(

menu -> alarm -> relay function

The alarm counter displays a date 
in the range of 1970. 
 
In the display (footer) appears 
again and again 

„no time“ 

When starting the device, no 
correct date / time was set. 

-  Set time and date correct 

(

menu -> settings -> date / 

time

Via Web interface (

network

activate a time server or 
change settings manual

  

The display shows 

∞Ω

 instead of 

the measured value 

The associated sensor has a 
sensor break in one or more wires 

Check sensor wires and replace if 
necessary 

2-wire Pt100 / Pt1000 sensor 
connected and 3-wire set in the 
configuration 

Check sensor. Change setting to 
2-wire with associated line 
resistance. 

The display shows 

0

 instead of 

the measured value 

The associated sensor has a 
sensor short circuit between 2 
wires. 

Check sensor wires and replace if 
necessary 

Display shows nothing 

Supply voltage not connected 

Fuse has tripped 

Devise has an internal defect 

Connect supply voltage 

Replace fuse 

Send in the device for repair 

„>>>“ or „<<<“ is displayed 
instead of the measured value 

Sensor value is greater (800°C) or 
less (-200°C) than measuring 
range 

Check sensor and replace if 
necessary 

Display is to dark 

The display is dimmed after the 
set time (

menu -> settings -> 

dimming time

), the set brightness 

is too low (

menu -> settings -> 

brightness

Increase the dimming time (

menu 

-> settings -> dimming time

), 

increase the display brightness 
(

menu -> settings -> brightness

)  

Device cannot be parameterized 
 
The display shows “code lock” for 
each parameter 

Code lock active 

In case of problems with the code 
lock (code forgotten), the 
protection can be switched off and 
the code can be reset to 504 by 
keeping the button pressed up 
(approx. 5s) when switching on 
the supply voltage. Now the code 
lock can be reset. 

No access via ethernet 

DHCP is on, but no IP address 
has been assigned 

Check the DHCP server or set a 
manual IP address 

Invalid network area 

Check the address range of the IP 
address and the subnet mask 

No parameters can be changed 
via the browser 

User administration active and no 
write access for current user 
available 

Assign write rights to the current 
user or disable user 
administration. If the admin 
password is not known, the user 
administration can be deactivated 
on the device. Disconnect the 
device from the supply voltage, 
push the button up, connect the 
supply voltage and hold the 
button (approx. 5s), reset the user 
administration. 

 

Содержание T224390

Страница 1: ...ature Relays and MINIKA Mains Monitoring Digital Panelmeters MINIPAN Switching Relays and Controls Measuring Transducers Grid and Plant Protection Operating Manual TR640IP updated 2019 09 24 sm from Firmware 0 00 TR640IP 12760 0702 00 Page 1 18 www ziehl de Pt100 Pt1000 PTC temperature relay with integrated webserver and display ...

Страница 2: ... 3 2 Call via web browser 7 9 4 Wire line adjustment 8 10 Operation 8 10 1 Program selection 8 10 2 Description of the parameters 10 10 3 Code lock code reset 11 10 4 Description of the display pages 12 10 4 1 Measured value page 1 3 12 10 4 2 Sensor to alarm assignment 2 3 12 10 4 3 Info page 3 3 12 10 5 Special functions 12 10 5 1 2 of x 12 10 5 2 Rate of change of temperature ROCOT 12 10 5 3 Cy...

Страница 3: ... Display and controls 1 Display K1 K4 white font relay released yellow font relay energized coloured bar below the relay name bar increasing delay alarm on active bar decreasing delay alarm off active bar flashes red manual intervention necessary alarm can be reset push button up or external switch on Y1 Y2 M relay is in manual mode depending on the colour of the relay name relay energized yellow ...

Страница 4: ...ply AC DC 24 270V Integrated web server for the measurement query configuration and for firmware updates Functions settings Alarm Each sensor can be assigned to each alarm relay K1 K4 o However only equivalent sensor types can be assigned to the same alarm That means Pt100 and Pt1000 sensors can be combined but not PTC at the same time o Caution The first parameterized sensor specifies the alarm t...

Страница 5: ... Ethernet socket for network cable 7 Important Information DANGER Hazardous voltage Will cause death or serious injury Turn off and lock out all power supplying this device before working on this device If the temperature sensors are installed in transformers or motors with a voltage 300V they must have a reinforced or double insulation suitable for the measurement All wires sensors reset ethernet...

Страница 6: ...to security in perfect condition If in any case the information in the instruction manual is not sufficient please contact our company or the responsible representative To maintain this condition you must observe the safety instructions in this instruction manual titled Important Information Failure to follow the safety instructions may result in death personal injury or property damage to the equ...

Страница 7: ...the language date and time can be changed at any time in the menu settings language date time or via web browser 9 3 Device on the network If the TR640IP is connected to a network via Ethernet the measured values and parameterization can be made via the web browser on a computer Basic knowledge of network technology is required for the configuration 9 3 1 Find the device in the network Network wit...

Страница 8: ...alarms 1 00 Trafo save 3x Pt100 same settings as Pr1 TR250 1T Pt100 2T Pt100 3T Pt100 4T off 5T off 6T off K1 fan with cyclic test K2 pre alarm K3 tripping K4 sensor device error 1 01 Trafo save 1x Pt100 2x PTC same settings as Pr3 TR250 1T Pt100 2T PTC 3T PTC 4T off 5T off 6T off K1 fan with cyclic test K2 pre alarm K3 tripping K4 sensor device error 1 02 Trafo save 3x Pt100 same settings as Pr4 ...

Страница 9: ...t100 4T Pt100 5T Pt100 6T Pt100 K1 sensor 1T K2 sensor 2T K3 sensor 3T K4 sensor 4T 3 01 other 6x PTC Single allocation 1T PTC 2T PTC 3T PTC 4T PTC 5T PTC 6T PTC K1 sensor 1T K2 sensor 2T K3 sensor 3T K4 sensor 4T 3 02 other 6x Pt100 1T Pt100 2T Pt100 3T Pt100 4T Pt100 5T Pt100 6T Pt100 K1 sensor 1T 2T 3T K2 sensor 1T 2T 3T K3 sensor 4T 5T K4 sensor 4T 5T Tip When a program is changed all paramete...

Страница 10: ...s back If a PTC is assigned to the alarm fixed reset values for PTC thermistors are used 199 9 800 0 C Delay alarm on Delay time between reaching the alarm on value and switching the relay 00 00 59 59 mm ss Delay alarm off Delay time between reaching the alarm off value and switching the relay 00 00 59 59 mm ss Relay function Function how the relay should behave in case of an alarm On at alarm off...

Страница 11: ...IP address in the network Subnet mask Manual setting of the subnet mask Settings Language Setting of the language of the display German English Date Setting the current date time Setting the current time Display interval Duration to update the display 0 1 2 0 s Brightness Display brightness 20 100 Dimming time Duration until the display brightness is reduced 00 10 59 59 mm ss Factory settings Load...

Страница 12: ... sensor error short circuit or sensor break Alarm state of the relays can be seen Kx white relay dropped Kx yellow relay energized Set alarm limit 10 4 3 Info page 3 3 Currently installed firmware version Currently selected program Reset input 0 open 1 closed Current IP address of the device Actual voltage current values of the analogue outputs 10 5 Special functions 10 5 1 2 of x For each alarm t...

Страница 13: ...ersion is available If the device is not connected to the internet the new firmware can be downloaded from the homepage www ziehl com Then the update file can be selected under system manual installation select firmware and carried out via the button manual update installation 10 8 Alarm counter There are separate alarm counters for each alarm These alarm counters store the last 20 shutdowns with ...

Страница 14: ...l defect Connect supply voltage Replace fuse Send in the device for repair or is displayed instead of the measured value Sensor value is greater 800 C or less 200 C than measuring range Check sensor and replace if necessary Display is to dark The display is dimmed after the set time menu settings dimming time the set brightness is too low menu settings brightness Increase the dimming time menu set...

Страница 15: ... 15 A sluggish Rated operational current AC 15 Ie 3 A Ue 250 V DC 13 Ie 2 A Ue 24 V DC 13 Ie 0 4 A Ue 120 V DC 13 Ie 0 2 A Ue 240 V UL electrical ratings 250 V ac 3 A general use 240 V ac 1 4 hp 2 9 FLA 120 V ac 1 10 hp 3 0 FLA C300 Relay outputs K1 alarm 1 Change over Switching voltage max AC 300 V DC 300 V Inrush current normally open NO AC 25 A 4s 50 A max 1s 10 ED Min voltage current 12 V 10 m...

Страница 16: ...me 100 Reinforced Insulation safe separation Us relay 6 mm DC 3540V Us sensor inputs 6 mm DC 3540V Us electronics reset ethernet 6 mm DC 3540V Sensor inputs relay 6 mm DC 3540V Sensor inputs electronics reset ethernet 6 mm DC 3540V relay ethernet 6 mm DC 3540V Basic insulation Relay Relay 3 mm DC 3540V No galvanic separation Analogue outputs reset ethernet Ethernet interface RJ45 connection Speed ...

Страница 17: ...50 Hz 5 g Housing Construction type V6 distribution board Mounting depth 55 mm Width 6 TE Dimension B x H x T 105 x 90 x 58 mm Wiring connections single strand 1 x 0 34 1 5 mm AWG 22 14 Finely stranded with wire end ferrule 1 x 0 1 1 0 mm AWG 27 16 Stripping length specify torque 8 mm 0 5 Nm Protection class housing terminals IP 30 IP20 Mounting Snap on fastening on 35 mm mounting rail acc EN 60 7...

Страница 18: ...se 3 Riegel bar for snap mountin 4 Plomben Lasche latch for sealing 5 Frontplatteneinsatz front panel 6 Kennzeichen für unten position downward 7 Riegel bei Wandbefestigung mit Schrauben Riegelbohrung Ø 4 2 mm for fixing to wall with screws Ø 4 2 mm 48 58 45 3 61 8 16 5 90 Option 105 98 116 70 1 2 4 5 6 7 3 ...

Отзывы: