Error no.
Error text
Error cause
M S
395
MP:ERR_EXT active
Error:
Internal defect of the device, overcurrent in the power stage
●
●
13.5.7
Error 4xx
•
Trip abort to protect the frequency inverter
•
Voltage monitoring
•
Overvoltage Brake resistor / Brake-Chopper
•
Power stage temperature recording
•
Current monitoring
Error no.
Error text
Error cause
M S
410
ADC: Over current!
Error:
Maximum modulation of the analogue current converter, motor current
too high
Remedy:
Check the connection to inverter output for short-circuit,
check encoder connection for connection of encoder tracks,
check the phase position (U
R
U; V
R
V; W
R
W),
Check motor data in the "Motor name plate" menu,
Decrease "SPD_KP" ampli
fi
cation in the "Control system" menu,
Reduce ampli
fi
cation during start "K_START" in the "Start" menu
●
412
MOT:UVW fail
Error:
Motor test current not correct
Remedy:
Check the motor connection
Check the motor contactors
(see also "Special functions" chapter)
●
415
MOT: Current UVW
Error:
Motor fault current, earth fault
Remedy:
Check the motor connection
Check the encoder connection
●
●
420
MP: Temp. Fault
Error:
Excess heat in the power stage
Remedy:
Check the fan,
check the ambient temperature,
when installing the inverter in the switch cabinet, ensure it has suf
fi
cient
ventilation
●
●
431
MP: PWM fail
Error:
The pulse width modulation of the clock frequency is not switched on or
off
Remedy:
Check encoder connection
●
●
450
MP: Overload!
Error:
Nominal current of inverter exceeded by a factor of 1.8 for 10 s
Remedy:
Check motor data
Check calculation
Check the weight compensation
●
460
HY_OVERLOAD
only at ZETADYN 3-HY
Fault:
Maximum level of the internal current controllers
Remedy:
Check motor data
Check encoder type
Check the encoder connection
Check encoder resolution
Reduce machine speed
Check machine for overload
Info:
inverted Function
●
470
DC: U < UDC_MIN
Error:
Intermediate circuit has undercut the permissible value for "UDC_MIN"
(Menu "Power section") during travel
Remedy:
Check the setting for the "UDC_MIN! value in the "Power section"
menu,
check the inverter size,
Check the motor data
Voltage drop during the travel
Check the input phases
●
●
Original operating instructions
ZETADYN 3C
Error diagnosis
R-TBA08_03-GB 1619
Part.-No. 00163322-GB
140/204
Содержание ZETADYN 3BF
Страница 196: ...Original operating instructions ZETADYN 3C EU declaration of conformity R TBA08_03 GB 1619 Part No 00163322 GB 196 204 ...
Страница 197: ...Original operating instructions ZETADYN 3C EU declaration of conformity R TBA08_03 GB 1619 Part No 00163322 GB 197 204 ...
Страница 198: ...Original operating instructions ZETADYN 3C EU declaration of conformity R TBA08_03 GB 1619 Part No 00163322 GB 198 204 ...
Страница 199: ...Original operating instructions ZETADYN 3C EU declaration of conformity R TBA08_03 GB 1619 Part No 00163322 GB 199 204 ...
Страница 200: ...Original operating instructions ZETADYN 3C EU declaration of conformity R TBA08_03 GB 1619 Part No 00163322 GB 200 204 ...
Страница 203: ...Original operating instructions ZETADYN 3C R TBA08_03 GB 1619 Part No 00163322 GB 203 204 ...