The evacuation type is set in the menu
Parameter set 2
.
ZAdyn4C
2nd parameter set
F_PAR2
enter the evacuation type
set at the input ZE1, ZE2
or ZE3 of the ZETADYN 2
ZETADYN 2
ZAdyn4C
Menu INTERFACES
Value
Monitoring menu
ST
MOD_ST
ZETADYN 2
ZAdyn4C
Travelling menu
Value
Travelling menu
V_ZE1
(m/s)
V_4
V_ZE2
(m/s)
V_5
V_ZE3
(m/s)
V_6
ZETADYN 2
ZAdyn4C
Menu Controller
Value
Controller menu
K_no
leave at default value of the ZA-
dyn4C
SPD_KP
5
Mechanical installation
5.1
General notes
Danger!
It is forbidden to carry out work on electrically live parts.
In frequency inverters of the ZETADYN type, the intermediate circuit (terDC / -DC) is still live
even after switching off.
You must wait at least three minutes.
5.2
Replacement of the ZETADYN 2 with the ZAdyn4C
"
Remove all lines connected to the ZETADYN 2.
"
Remove ZETADYN 2.
"
Install ZAdyn4C. Observe the installation conditions described in the operating instructions!
Technical Information
Mechanical installation
R-TIA18_02-D-GB 2106
Part.-No. 00163466-D-GB
6/24