Wiring diagram forced ventilation
On-site connection must be made by the customer according to the wiring diagram in the separate
terminal box of the external ventilation.
6 Start-up
6.1
Operating conditions
"
The drive must be installed in a not free accessible machine room or a closed hoistway.
"
Be aware of the protection class speci
fi
ed on the name plate.
"
Do not operate the motor in an explosive atmosphere.
"
The ambient temperature may be within 0
°
C and +40
°
C.
"
Maximum permissible humidity 95 %, not wet.
"
Reduced cooling when installed 1000 m above sea level. Therefore, the torque by 1 % per
100 m must be reduced or the duty cycle time of 1.5 % per 100 m.
"
Please contact ZIEHL-ABEGG SE in case of orders deviating from the corresponding applica-
tion conditions.
6.2
First-time start-up
Before
fi
rst-time start-up, check the following:
"
Installation and electrical connection have been properly completed.
"
Safety devices are installed.
"
All leftover installation materials and other foreign materials have been removed.
"
The protective earth is connected.
"
Motor protection correctly connected and operative.
"
Cable entries closed.
"
Mounting, installation position and accessories are o.k.
"
Connection data corresponds to the data on the name plate.