5.3
Motor connection
CAUTION!
"
The drive must not be connected to the mains supply without a frequency inverter!
"
The motor is permitted to be used at frequency inverters with a maximum DC-link voltage
of < 750 V DC!
"
A shielded motor cable has to be used.
"
The screen has to be connected on both ends.
"
The maximum motor cable length is 25 m.
"
If no other agreement was met, the absolute encoder offset is set to 0 To do that, connect the
direct current with
U to +
and
V and W to -
.
"
The motor connection lines U, V and W have to be connected on the motor and inverter side to
the correct phases and must not be changed. Otherwise the motor may speed up uncontrolled.
"
The temperature monitoring of the motor has to connect to the frequncy inverter.
"
The admissible test voltage of temperature monitoring is maximum 2.5 V DC.
Mechanical connection conditions
Motor rated current
[A]
Terminal board
Thread
up to 20
M 8
M 25
> 20 - 25
M 8
M 32
> 25 - 35
M 8
M 32
> 35 - 50
M 8
M 40
> 50 - 63
M 8
M 40
Wiring diagram Motor
permissible tightening torque for bolts M8: 6 Nm
2ULJLQDORSHUDWLQJLQVWUXFWLRQV
ZAtop
–
model series SM225.40B
Electrical installation
A-TBA13_06-GB
Part.-No. 01009090-GB (
(8%'
)
9/72