Motor fault
Controllers period of operation at time of message:
With the
P
key can be switched between description of the
message and the Controllers period of operation at this time.
E.G. on place 3 which is past message
motor fault
.
00009:01:08
12.2
Messages and trouble shooting
A momentary pending alarm or error message is indicated by a blinking indicator and appears
alternately with the standard display.
Operating conditions are indicated by the status LED with
fl
ashing code.
internal State LED
11.02.2009
v_flash_explain.VSD
3 x
2 x
ON
OFF
4 x
5 x
6 x
1 x
7 x
8 x
9 x
Display
Code*
LED Code
Relais switches
**
Possible cause
Reaction of Controller
internal
Opera-
tion
Fault
Remedial measures
OFF
Line voltage available?
Unit switch OFF and automati-
cally ON when the voltage has
been restored
1
1
0
No enable
Switch OFF by external contact
(function
|
1D
|
= enable pro-
grammed for Digital In)
Factory sett.
AL
-
0
1
Controller did a factory set-
ting automatically (e.g. in
case of faulty parameter
data).
Warning message:
Operation with factory setting
EEP error
AL
-
0
1
fault EEP damaged
Operation with factory setting
EEP Corruption
AL
-
0
1
EEP data incorrectly
controller runs with the read
settings
MC Bootload
AL
-
0
1
Fault bootload process of
the motor controller. I.e.
the motor controller pro-
gram could not be loaded
or started.
Fault indication, cold start
(reset) of the control unit