9.12
Motor Setup
Motor Setup
Menu group Motor Setup
9.12.1
Setting motor rated current
MotorRatedCurr.
MotorRatedCurr.
When commissioning, you must set the motor to the rated current stated on the rating
plate.
The setting for the
“
DC brake level
”
(setting brake behaviour) refers to this setting.
Setting range: 0.0...device rated current / A
Factory setting: device rated current
9.12.2
Setting motor rated voltage
MotorRatedVolt.
MotorRatedVolt.
When commissioning, you must set the motor to the rated voltage stated on the rating
plate.
An adaptation can be made if the motor rated-voltage as the applied mains voltage is
lower (e.g. 3 ~ 230 V motor on 3 ~ 400 V mains).
Verify the output voltage using suitable measuring instruments.
Setting range: 0...500 V
Factory setting: 400 V
9.12.3
Adjustment of the U/f curve
Attention!
Settings for U/f characteristic may only be made when no motor modulation is present!
Edgefrequency
Edgefrequency
The maximum output voltage is attained during break edge frequency.
Adjustment range: 10.0 - 150.0 Hz
Factory setting: 50.0 Hz
In the case of special settings with
“
Edge frequency
”
>
“
Max. frequency
”
, due to higher
power losses it is possible that automatic power reduction occurs (Messages and
trouble shooting
“
Overload
”
).
Max. Frequency
Max. Frequency
Above the Edgefrequency, the frequency is merely increased up to the Maximum
frequency.
Adjustment range: 10.0 - 150.0 Hz
Factory setting: 50.0 Hz
Shutdown Freq.
Shutdown Freq.
Below the Shutdown Freq. the output is switched o
ff
(hysteresis approx. 1.5 % setting
“
Max. Frequency
”
) .
Adjustment range: 5.0 - 150.0 Hz
Factory setting: 5.0 Hz
Operating Instructions
Icontrol
–
model series FXDM
Programming
L-BAL-E036-GB 2022/47 Index 011