Please ask manufacturer for the individual harmonic oscillation levels of the current
as a percentage of the fundamental oscillation of the rated current.
Vibratory strength
(for vertical installation, i.e. cable inlet
down).
FXDM2.6...25 and FXDM32E...62E
Broadband noise (simulated life-endurance test) in accordance with EN 61373,
category 1 class B.
Shock test according to EN 61373, category 1
*
Regarding the mains connection, these devices are to be classi
fi
ed as category
“
C2
”
devices according to the relevant DIN
EN 61800-3. The increased requirements placed on electrical interference > 2 kHz for category
“
C1
”
devices are complied
with in addition.
14.1.1
Versions type-lines Icontrol
In IP54 for wall mounting
•
FXDM..
external terminal type AXG-1A(E), for start-up and setting necessary.
•
FXDM..A
internal LC-multifunction display with plain language text.
•
FXDM..AQ
internal LC-multifunction display with plain language text + main switch.
In IP20 for switch cabinet mounting
•
FXDM..E
external terminal type AXG-1A(E), for start-up and setting necessary.
•
FXDM..AE
internal LCD-Multifunction display with plain language text.
14.1.2
Max. loading dependent on: clock frequency, line voltage and ambient temperature
A load with the rated current stated in the type code is possible under adherence to the following rated
conditions.
With conditions deviating from it the following table is to be considered.
e.g. type: FXEM2.6
Rated current = 2.6 A
Rated conditions:
•
Line voltage 3 ~ 208 (-15 %)...415 V (+6 %)
•
Switching Freq. 6 / 8 kHz
•
max. 40
°
C ambient temperature
Power reduction for line voltage higher 3 ~ 415 V (+6 %) or increasing of clock frequency
The power losses occurring in the device increase at mains voltages
over 3 ~ 415 V
and increasing
clock frequencies. Therefore, it is necessary to carry out a power reduction under these conditions.
Performance reduction during elevated ambient temperatures
The unit
´
s maximum permissible ambient temperature is 40
°
C. Up to that temperature a load of the
quoted rated current is possible under rated conditions.
As the dissipation of the power loss (heat generation) arising in the device depends crucially on the
ambient temperature, the max. load must de
fi
nitely be reduced in cases where the ambient temper-
atures exceed 40
°
C! The average value measured during a 24 h period must be 5 K under the max.
ambient temperature. For installation in a switch cabinet, the device
’
s dissipation and its possible
affect on the ambient temperature must be taken into consideration (
Technical data)!
Maximal motor current for
|
6 kHz
|
depending on line voltage and ambient temperature (only
FXDM32...62)
Type
208 V (-15 %)...415 V (+6 %)
over 415 V (+6 %)...480 V (+10 %)
40
°
C
50
°
C
55
°
C
40
°
C
50
°
C
55
°
C
FXDM32A(E)(Q)
32.0 A
32.0 A
28.0 A
32.0 A
30.0 A
26.0 A
FXDM39A(E)(Q)
39.0 A
39.0 A
39.0 A
39.0 A
39.0 A
37.0 A
FXDM46A(E)(Q)
46.0 A
46.0 A
42.0 A
46.0 A
43.0 A
39.0 A
FXDM62A(E)(Q)
62.0 A
55.0 A
50.0 A
62.0 A
55.0 A
48.0 A
Operating Instructions