![ZIEHL-ABEGG Icontrol FXDM Series Скачать руководство пользователя страница 89](http://html1.mh-extra.com/html/ziehl-abegg/icontrol-fxdm-series/icontrol-fxdm-series_operating-instructions-manual_3733913089.webp)
Type
(Part-No.)
Rated cur-
rent*
Output
{1}
[A]
Rated cur-
rent
(
I
funda-
mental com-
ponent @
50 Hz)
Input
{1}
[A]
Recom-
mended
motor out-
put
{2}
[kW]
max. line
fuse
{3}
[A]
max. heat
dissipation
{1}
[W]
Noise ap-
prox.
{4}
[dB]
Weight
[kg]
Housing
protection
IP
FXDM39AE
(308081)
39
34.0 (31.5)
18.5
50
900
65.7
25.8
20
FXDM46A
(308088)
46
46 (-)
22,0
50
1050
65.7
26.3
54
FXDM46AQ
(308171)
46
46 (-)
22,0
50
1050
65.7
27.1
54
FXDM46AE
(308089)
46
46 (-)
22,0
50
1050
65.7
25.8
20
FXDM62A
(308092)
62
62 (-)
30,0
63
1250
65.7
26.3
54
FXDM62AQ
(308172)
62
62 (-)
30,0
63
1250
65.7
27
54
FXDM62AE
(308093)
62
62 (-)
30,0
63
1250
65.7
25.8
20
{1}
at line voltage 400 V / 50 Hz (cos
φ
0.8 Output), data for deviating line voltages on request
{2}
Example for power of a 4 pole motor. For the dimension of the frequency inverter size the rated current of the motor is
crucial!
{3}
Max. supply side line fuse according to DIN EN 60204-1 classi
fi
cation VDE0113 chapter 1
{4}
Sound power level A-weighted by internal fan (- no indication)
-
no speci
fi
cation
Line voltage*
3 ~ 208...480 V (-15 up to +10 %), 50/60 Hz
Maximal output voltage
approx. 95 % of U
Line
, Operation with Overmodulation approx. 100 % of U
Line
Maximal output frequency
150 Hz
Power factor
> 0.9
Switching Freq.
6 / 8 / 10 / 16 kHz
Input resistance for sensor or signal set for
the rotational speed
for 0 - 10 V input: R
i
>100 k
Ω
for 4 - 20 mA input: R
i
= 100
Ω
Voltage supply e.g. for sensors
+24 V
±
20 %, I
max
120 mA (for connection to an external AXG terminal minus
approx. 50 mA)
Output (0 - 10 V)
I
max
10 mA (short-circuit-proof)
max. contact rating of the internal relay
2 A / 250 VAC
Max. permissible ambient temperature
40
°
C (up to 55
°
C with derating)
Min. permissible ambient temperature
0
°
C (if mains voltage is not switched off up to -20
°
C)
Permissible temperature range for storage
and transport
-30...+80
°
C
Max. permissible installation height
above 0...4000 m amsl. Above 1000 m amsl the rated current is to be reduced by 5
% / 1000 m
Permissible rel. humidity
85 % no condensation
Electromagnetic compatibility for the
standard voltage 230 / 400 V according to
DIN IEC 60038
Interference emission EN 61000-6-3 (domestic household applications)
Interference immunity EN 61000-6-2 (industrial applications)
Harmonics current
For devices < 4 A according EN 61000-3-2
For devices
≥
4 A and
≤
16A according EN 61000-3-2 for a
“
professional unit
”
Electrical installation / harmonics current
For devices > 16 A and
≤
75 A according EN 61000-3-12
(
Electrical installation / harmonics current and line impedance)
Operating Instructions
Icontrol
–
model series FXDM
Enclosure
L-BAL-E036-GB 1422 Index 008
Part.-No. 00154773-GB
89/96