Connection of external Terminal type AXG-1A(E)
An external terminal is required for starting-up and setting-up versions that do not have an integrated
terminal.
•
Model AXG-1A, Part-No. 349034 for wall mounting
•
Model AXG-1AE, Part-No. 349008 for panel mounting
Connection Terminal Type
AXG-1A(E)
The connection is made via a 4-strand line at the terminals of plug (D-, D+, GND and
+24 V).
e.g., telephone
fl
ex e.g. J-Y (St) Y 2x2x0.6 (or similar), maximum line length ca. 250 m.
- Voltage supply: Terminal
“
24 V
”
,
“
GND
”
, (I
max
, for terminal approx. 50 mA)
- Signal
“
D+
”
and
“
D-
”
(RS 485)
If the Modbus
®
interface is used for network a
“
Z-Modul-A
”
(Part.-No. 380054) is necessary to use an
external terminal at the same time.
5.12
Digital inputs (D1, D2)
Various functions can be allocated to the digital inputs
“
D1
”
and
“
D2
”
(
IO Setup: Functions
summary of the digital inputs). Activation via
fl
oating contacts (a low voltage of ca. 24 V DC is
connected).
Danger due to electric current
Never apply line voltage to the digital input!
It is not permissible to connect inputs of several devices to each other!
5.13
Relay outputs (K1, K2)
Various functions can be allocated to the relay outputs
“
K1
”
and
“
K2
”
(
IO Setup: function and
inverting relais outputs). Max. contact rating
technical data and connection diagram.
Connection of the
fl
oating contacts of relay
“
K1
”
to the terminals 11, 14, 12. Connection of the
fl
oating
contacts of relay
“
K2
”
to the terminals 21, 24, 22.
5.14
Communication
5.14.1
Networking via MODBUS-RTU
The device comes equipped with a RS-485 interface for networking via MODBUS. Conntection at:
“
A
(D+)
”
,
“
B (D-)
”
and
“
GND
”
.
The address must be set in the
“
IO Setup
”
menu.
Information
A maximum of 64 members can be directly connected to one another, and another 63 members via a
repeater.
5.14.2
RS-485 - network design and interface parameter
Please ensure the correct connection; i.e. "A (D+)" must always be connected to "A (D+)" of the next
devices. The same applies to "B (D-)" .
In addition, a "GND" connection must be established, as dissimilar potential (over 10 V!) will lead to
the destruction of the RS-485 interface (e.g. lightning).
Operating Instructions
Icontrol
–
model series FXDM
Electrical installation
L-BAL-E036-GB 1422 Index 008
Part.-No. 00154773-GB