11.2.1
Connection suggestion for several motors with motor protection units type STDT
•
Full motor protection by switch-off when activating the attached thermostat switches
“
TB
”
. Reset after
malfunction by key press.
•
Line protection: A thermal over current sensor and a magnetic short circuit releasing elements are the
parts of the integral line protection. Adjustment to the thermal overcurrent sensor to the max. permissible
current of the connected cable (max. line fuse 80 A).
•
No cut-off if the mains supply is interrupted
3~ Controller
U
P
E
V
W
N
L1
L2
L3
L3
N
L2
L1
PE
3~ 208 .. 415 V
4 mm²
KT00005H
27.09.2007
1
3
2
4
6
I >
5
STDT16
TB
TB
I >
I >
3~ Motor
M
3~
PE
V
W
U
TB
TB
4 mm²
1,5 mm²
1
3
2
4
6
I >
5
STDT16
TB
TB
I >
I >
3~ Motor
M
3~
PE
V
W
U
TB
TB
4 mm²
1,5 mm²
1
3
2
4
6
I >
5
STDT16
TB
TB
I >
I >
3~ Motor
M
3~
PE
V
W
U
TB
TB
4 mm²
1,5 mm²
Y/
Y/
Y/
Consider max. terminal load
Operating Instructions!
(General example, data for the connection of the controller dependent on the used type of device)
Operating Instructions
Dcontrol
–
model series PKDM6..80
Enclosure
L-BAL-E143-GB 1914 Index 009
Part.-No.
36/40