9.1.2
Operation with two variable output voltages (two steps)
DIP2 =
|
OFF
|
for setting via external signall.
Switchover between two steps via external potential-free contact possible.
•
Step 1
(low speed). When there is no input signal connected to the input terminal
“
E1
”
, then the unit
supplies the output voltage set by
“
n-min
”
.
•
Step 2
(high speed). When the terminal
“
A1
”
(+10 V) is connected with the input terminal
“
E1
”
then
the units supplies the output voltage set by
“
n-max
”
.
n-min
nM
100 %
1
t
n-max
1
2
05.02.2008
v_diagr_2stufen.VSD
"A1" (+10 V)
"E1"
nMotor
= "n-max"
nMotor
= "n-min"
1
2
05.02.2008
v_schalter_2stufen.VSD
Operating Instructions
Dcontrol
–
model series PKDM6..80
Setting for operation