![ZIEHL-ABEGG Dcontrol PKDM10 Скачать руководство пользователя страница 33](http://html1.mh-extra.com/html/ziehl-abegg/dcontrol-pkdm10/dcontrol-pkdm10_operating-instructions-manual_933533033.webp)
Version: housing IP20, for switch cabinet mounting without internal semiconductor fuses
Type
Part-No.
Rated cur-
rent
{1}
Rated tem-
perature
max. line
fuse
{2}
Semiconductor
fuse on site
{3}
max. heat
dissipation
{4}
Weight
[A]
[
°
C]
[A]
[W]
[kg]
PKDM25E
304622
25
50
35
FF50 A D02
(e.g. fuse kits
349030)
260
7.4
PKDM35E
304623
35
50
50
FF63 A D02
(e.g. fuse kits
349031)
430
7.5
PKDM50E
304635
50
50
63
FF100 A NH00
(e.g. fuse kits
349032)
160
13.8
PKDM80E
304636
80
50
100
FF160 A NH00
(00089793)
255
15.4
{1}
Rated current
current speci
fi
cation rating plate @ rated voltage, @ rated temperature
{2}
Max. supply side line fuse according to DIN EN 60204-1 classi
fi
cation VDE0113 chapter 1
{3}
Semiconductor fuse not in the scope of supply, as accessories available. For protection of damages in the case of short-
circuits installation on site recommended
{4}
At rated voltage, values for different speci
fi
cations on request
Line voltage
3 ~ 208...415 V (-15 up to +10 %), 50/60 Hz
Rated voltage
400 V
Stepless controlled output volt-
age
approx. 20...100 % of connected line voltage
Min. motor current
for PKDM6: 0.2 A, for PKDM10...80: 0.5 A
Input resistance for sensor or
signal set for the rotational
speed
for 0 - 10 V input: R
i
>100 k
Ω
for input 4 - 20 mA: R
i
= 250
Ω
Voltage supply e.g. for sen-
sors
+24 V
±
20 %, I
max
120 mA (for connection to an external AXG terminal minus approx. 50 mA)
Output (0 - 10 V)
I
max
10 mA (short-circuit-proof)
Contact rating of the internal
relay
max. AC 250 V 2 A
Max. permissible ambient tem-
perature for operation
55
°
C
Min. permissible ambient tem-
perature
0
°
C (if mains voltage is not switched off up to -20
°
C)
Max. permissible installation
height
0...4000 m amsl
≤
1000 m: no limitation
> 1000 m: max. permissible output current = current indication name plate minus 5 % / 1000 m
> 2000 m: max. permissible line voltage = max. voltage indication name plate minus 1.29 % /
100 m
Permissible rel. humidity
85 % no condensation
Electromagnetic compatibility
for the standard voltage 230 /
400 V according to IEC 60038
Interference emission EN 61000-6-3 (domestic household applications)
Interference immunity EN 61000-6-2 (industrial applications)
Max. leakage current accord-
ing to the de
fi
ned networks of
EN 60990
< 3.5 mA
Harmonics current
For devices
≤
16A
According EN 61000-3-2 (for a
“
professional device
”
)
Electrical installation / harmonics current
For devices > 16 A and
≤
75 A
according EN 61000-3-12
(
Electrical installation / harmonics current and line impedance)
Operating Instructions
Dcontrol
–
model series PKDM6..80
Enclosure
L-BAL-E143-GB 1914 Index 009
Part.-No.
33/40