7.2
Select operation mode
Simple installation is possible through the use of modes of operation.
Mode
Signal or Sensor
(input)
Function
1.00
-
Speed controller, setting the output voltage by internal potentiometer
“
set
”
.
1.01
Signal 0 - 10 V (E1)
Speed controller, setting the output voltage by external signal
(factory
setting)
.
2.01
Sensor KTY81-210 / PT1000 (E1)
(for PT1000 dipswitch
|
3
|
to
“
ON
”
)
Temperature control airconditioning and refrigeration.
2.02
1x Sensor KTY81-210 (E1)
1x Sensor KTY81-210 (E1)
(for PT1000 dipswitch
|
3
|
to
“
ON
”
)
Temperature control with 2 sensors.
Automatic control to the temperature sensor with higher value.
3.01
Sensor type MBG.. (E1)
Pressure control condensers (refrigeration)
3.02
1x sensor type MBG.. (E1)
1x sensor type MBG.. (E2)
Pressure control condensers (refrigerant technology) with 2 sensors.
Automatic control to the pressure sensor with higher value (for two
circuit condensers).
7.3
Dipswitch for operation as Speed controller:
1.00
,
1.01
For operation as a Speed controller (DIP
|
1
|
=
|
OFF
|
) the output voltage is set manually by adjusting
the built-in potentiometer, by an external potentiometer or external signal.
The desired function is determined with dipswitch
S1
.
Position factory setting for all dipswitches =
|
OFF
|
.
DIP
Function
DIP =
|
OFF
|
DIP =
|
ON
|
1
Selection:
Speed controller / P-Controller
RPM controller
P-Controller
2
Signal source of control
Setting of output voltage by external signal
to
“
E1
”
(Internal potentiometer
“
set
”
without func-
tion)
Setting the output voltage by internal po-
tentiometer
“
set
”
3
Signal type at E1 (E2)
0 - 10 V, 0 - 20 mA*
4 - 20 mA
4
Inverting signal input E1 (E2)
Inverting not active:
0 - 10 V, 0 - 20 mA*, 4 - 20 mA
Inverting active:
10 - 0 V, 20 - 0 mA* 20 - 4 mA
5
Minimum speed cut off
not active
active
6
Hardstart function
not active
active
7
Input E2
Input E2 not active
Input E2 active
8
Function signal output
“
Analog
Out 1
”
Constant voltage
“
+ 10 V
”
for external
potentiometer
0 - 10 V
modulation 0 - 100 %
9
60 Hz allocation
automatic detection
60 Hz
fi
x
10
Phase failure detection
Detection active
Detection not active
*
By external wiring with a resistor (499
Ω
/ 0,25 W) between the terminals
“
E1
”
and
“
GND
”
parallel to the input signal,
activation with a 0...20 mA signal is possible.
Operating Instructions
Dcontrol
–
model series PKDM6..80
Base setup
L-BAL-E143-GB 1914 Index 009
Part.-No.
21/40