8.3
Excerpt from the MODBUS register description for ECblue Basic and Basic frequency
inverters I/Fcontrol
The examples listed here represent just a small selection of frequently used registers. The complete
MODBUS register description can be downloaded from our web site.
8.3.1
MODBUS Register overview
Holding Registers
•
MB Holding Register 1, Address: h0 = PIN input
•
MB Holding Register 2, Address: h1 = Control
•
MB Holding Register 3, Address: h2 = Speed control
•
MB Holding Register 4, Address: h3 = COM Parameter
•
MB Holding Register 5, Address: h4 = Controlmode
•
MB Holding Register 6, Address: h5 = Set Intern1
•
MB Holding Register 7, Address: h6 = Set Intern2: 1/min
•
MB Holding Register 8, Address: h7 = Min. Speed: 1/min
3)
•
MB Holding Register 9, Address: h8 = Max. Speed: 1/min
•
MB Holding Register 10, Address: h9 = Set Intern3: 1/min
•
MB Holding Register 11, Address: h10 = Inverting
•
MB Holding Register 12, Address: h11 = E11 Min
•
MB Holding Register 13, Address: h12 = E12 Max
•
MB Holding Register 14, Address: h13 = E1 Function
•
MB Holding Register 15, Address: h14 = D1 Function
•
MB Holding Register 16, Address: h15 = K1 Function
•
MB Holding Register 17, Address: h16 = Controller Setup Flags
•
MB Holding Register 18, Address: h17 = Communication Watchdog
•
MB Holding Register 19, Address: h18 = Limit
•
MB Holding Register 20, Address: h19 = Radio network code
•
MB Holding Register 26, Address: h25 = Ramp timing
•
MB Holding Register 31, Address: h30 = Suppression
•
MB Holding Register 32, Address: h31 = Range1 Min
•
MB Holding Register 33, Address: h32 = Bereich1 Max
•
MB Holding Register 34, Address: h33 = Range2 Min.
•
MB Holding Register 35, Address: h34 = Rereich2 Max.
•
MB Holding Register 36, Address: h35 = Range3 Min.
•
MB Holding Register 37, Address: h36 = Rereich3 Max.
Input Registers
•
MB Input Register 1, Address: i0 = Firmware
•
MB Input Register 2, Address: i1 = Product code 1
•
MB Input Register 3, Address: i2 = Parameterset ID (from FW 13)
•
MB Input Register 4-9, Address: i3 - i8 = Unique Device Signature 0 - 5
•
MB Input Register 10, Address: i9 = Parameterset Index (from FW 13)
•
MB Input Register 11, Address: i10 = Operation condition 1
•
MB Input Register 12, Address: i11 = Operation condition 2 (from FW 13)
•
MB Input Register 13, address: i12 = error status
•
MB Input Register 14, Address: i13 = Reserve
•
MB Input Register 15, Address: i14 = Speed
•
MB Input Register 21, Address: i20 = DC voltage
•
MB Input Register 22, Addresse: i21 = Line voltage
•
MB Input Register 23, Address: i22 = IGBT-temperature
•
MB Input Register 24, Addresse: i23 = inside temperature
•
MB Input Register 25, Address: i24 = MCU temperature
•
MB Input Register 26, Address: i25 = Motor temperature
•
MB Input Register 27, Address: i26 = E1 input
•
MB Input Register 28, Address: i27 = Modulation
•
MB Input Register 31, Address: i30 = Event
•
MB Input Register 32, Address: i31 = Event number
•
MB Input Register 34, Address: i33 = Motor input power
•
MB Input Register 50, Address: i49 = Inquiry PIN protect level
Operating Instructions
AM-CAN-OPEN
–
model series
Enclosure
L-BAL-E199-GB 1846 Index 005
Part.-No. 00163405-GB
22/28