Manufacture Speci
fi
c Area
Index
Sub
Index
Name
Type
At.
basic setting
Remarks
0x2000 0
Holding register
U8
RO
50
Count Register
0x2000 1
h0 - Holding reg. 1
U16
RWW 0
h0 = PIN input
0x2000 2
h1 - Holding reg. 2
U16
RWW 0
h1 = Control
0x2000 3
h2 - Holding reg. 3
U16
RWW 0
h2 = Speed control
...
...
...
...
...
...
...
0x2000 50
h49 - Holding reg. 50
U16
RWW 0
-
0x2001 0
Input registers
U8
RO
50
Count Register
0x2001 1
i0 - Input reg. 1
U16
ROR
0
i0 = Firmware
0x2001 2
i1 - Input reg. 2
U16
ROR
0
i1 = Productcode 1
0x2001 3
i2 - Input reg. 3
U16
ROR
0
i2 = Parameterset ID
...
...
...
...
...
...
...
0x2001 50
i49 - Input reg. 50
U16
ROR
0
49 = Inquiry PIN Protectlevel
0x2002 0
Production registers
U8
RO
...
Count Register
0x2002 1
...
U32
RO
0
...
...
...
...
...
...
0x2002 ...
...
U32
RO
0
All data pre
fi
xed with
“
0x
”
are hexadecimal.
access Attribute
Attributes
SDO
PDO (Mapping)
RO
read only
no access
WO
write only
no access
RW
read / write
no access
ROR
read only
read only
RWR
read / write
read only
RWW
read / write
write only
6.2.3
Prede
fi
ned settings by the address switch
The following settings are preset by the address switch (address: 1-126)
COB_ID / NODE_ID
Value
SYNC Message
0x080
TIME Message
0x100
Emergency
0x080 + NODE_ID
SDO client -> server
0x600 + NODE_ID
SDO server -> client
0x580 + NODE_ID
RX PDO0
0x200 + NODE_ID
RX PDO1
0x300 + NODE_ID
RX PDO2
0x400 + NODE_ID
RX PDO3
0x500 + NODE_ID
TX PDO0
0x180 + NODE_ID
TX PDO1
0x280 + NODE_ID
TX PDO2
0x380 + NODE_ID
TX PDO3
0x480 + NODE_ID
All data pre
fi
xed with
“
0x
”
are hexadecimal.
NODE ID comes from the switch position
Operating Instructions
AM-CAN-OPEN
–
model series
Communication
L-BAL-E199-GB 1846 Index 005
Part.-No. 00163405-GB