10
Menu table
Information
The individually made programming can be saved with PIN 9091 and restored with PIN 9090
(Quickinfo Menu- PIN).
Attention!
Entering PIN 9095 completely resets the device back into its delivered condition. Any
changes that have been made to the settings are thus lost!
S:20.0
°
SH:94%
▼
▲
Ventilation
▼
▲
Alarm
▼
▲
Heating
▼
▲
Installation
P
↓
↑
▼
+
▲
=
|
ESC
|
P
↓
↑
▼
+
▲
=
|
ESC
|
P
↓
↑
▼
+
▲
=
|
ESC
|
P
↓
↑
▼
+
▲
=
|
ESC
|
P*
5 sec
↓
↑
▼
+
▲
=
|
ESC
|
Parameter
Factory setting
Compartment setting
Quick Info
Setpoint
20
°
C
E2
81.6
-
Temp. min. Value
18.7
-
Temp. max. Value
25.9
-
Reset Min-Max
OFF
Language
D
PIN
- - - - -
Version
1.04
-
OTC
00046:37:12
-
OTM
00046:37:12
-
Ventilation
Setpoint
20
°
C
Pband
4.0 K
Min. Speed
20 %
Max. Speed
100 %
Shutter offset
-1.0 K
Shutter Pband
2.5 K
Shutter Min.
0 %
Shutter max.
100 %
Setp. Derating
OFF
Alarm
Alarm Minimum
10.0
°
C
Alarm Maximum
35.0
°
C
Alarmdifference
5.0 K
Alarm pause
60 min
Alarmlist
OFF
Heating
Heating offset
-2.0 K
Heat. hysteresis
0.5 K
Heating Pband
*2.0 K
Heating minimum
*0 %
Heating maximum
*100 %
- = Only display, no adjustment possible
* = Setting only in heating mode 2 (0...10 V)
Operating Instructions
Acontrol
–
model series PTE-6AHQ / PTE-10AHQ
Menu table
L-BAL-E044-GB 1911 Index 003
Part.-No.
28/36