Positive hysteresis value =
Heating function
0
1
12.08.2008
v_heiz_pos_hys_abs.vsd
H
S
A [°C]
H
Hysteresis
S
Setpoint
A
Compartment temperature
0
Heating OFF
1
Heating ON
Negative hysteresis value =
Cooling function
0
1
12.08.2008
v_heiz_neg_hys_abs.vsd
H
S
A [°C]
H
Hysteresis
S
Setpoint
A
Compartment temperature
0
Heating OFF
1
Heating ON
9.5.2
Controlling the heating via the 0...10 V signal (linear)
Example for controlling the heating via the 0 - 10 V signal (mode 2 = proportional controller)
The heating, activated through the 0 - 10 V signal, is indicated in the display with the
fi
re symbol as
soon as the activation exceeds
“
0 %
”
.
The
“
K2
”
heating relay is connected in parallel in order to activate, for example, a gas valve.
Heating offset
Heating offset
Heating related to the ventilation setpoint (i.e. offset adjustment in Kelvin)
in heating installation menu input:
“
0
”
=
“
E1
”
Current heating value = Current ventilation value (i.e., temperature from sensor on
input
“
E1
”
)
Setting range: -10.0...+10.0 K
Factory setting: -2.0 K
or
Heating Setpoint
Heating Setpoint
Heating is adjustable as a separate setpoint (i.e. in
°
C)
in heating installation menu input: 1 =
“
E2
”
Current heating value from sensor on input E2
Setting range: -10.0...+40.0
°
C
Factory setting: -2.0
°
C
Heating Pband
Heating Pband
Setting range: 0.1..10.0 K
Factory setting: 2.0 K
Heating minimum
Heating minimum
Setting range: 0...100 %
Factory setting: 0 %
Heating maximum
Heating maximum
Setting range: 0...100 %
Factory setting: 100 %
Operating Instructions
Acontrol
–
model series PTE-6AHQ / PTE-10AHQ
Settings for operation
L-BAL-E044-GB 1911 Index 003
Part.-No.
26/36