9.3.3

Setting with refrigerant medium table
Information

Calculation for relative pressure (differential measurement of pressure relative to ambient pressure).

Set

0

%

5

%

10

%

15

%

20

%

25

%

30

%

35

%

40

%

45

%

50

%

55

%

60

%

65

%

70

%

75

%

80

%

85

%

90

%

95

%

100

%

MBG-30I

[bar]

0.00

1.50

3.00

4.50

6.00

7.50

9.00

10.50 12.00 13.50 15.00 16.50 18.00 19.50 21.00 22.50 24.00 25.50 27.00 28.50 30.00

I

[mA]

4.0

4.8

5.6

6.4

7.2

8.0

8.8

9.6

10.4

11.2

12.0

12.8

13.6

14.4

15.2

16.0

16.8

17.6

18.4

19.2

20.0

R12

[

°

C]

-30.09 -6.28

8.11

18.90 27.70 35.22 41.84 47.80 53.23 58.23 62.90 67.27 71.39 75.30 79.01 82.57 85.97 89.24 92.39 95.43 98.37

R13

[

°

C]

-81.99 -62.83 -51.33 -42.75 -35.77 -29.82 -24.60 -19.91 -15.65 -11.72 -8.07

-4.65

-1.43

1.61

4.51

7.27

9.91

12.45 14.89 17.25 19.52

R13b1

[

°

C]

-58.14 -36.81 -23.92 -14.26 -6.38

0.36

6.29

11.63 16.49 20.97 25.15 29.06 32.75 36.25 39.58 42.76 45.81 48.74 51.56 54.28 56.92

R22

[

°

C]

-41,11 -19.52 -6.57

3.09

10.95 17.65 23.53 28.80 33.60 38.02 42.13 45.97 49.59 53.02 56.27 59.38 62.35 65.20 67.95 70.59 73.15

R23

[

°

C]

-82.44 -64.82 -54.36 -46.61 -40.34 -35.02 -30.36 -26.20 -22.43 -18.96 -15.75 -12.75 -9.94

-7.27

-4.75

-2.35

-0.05

2.15

4.26

6.30

8.26

R32

[

°

C]

-52.53 -32.24 -20.30 -11.51 -4.44

1.54

6.76

11.41 15.62 19.47 23.03 26.35 29.47 32.40 35.18 37.83 40.35 42.76 45.07 47.30 49.44

R114

[

°

C]

3.45

30.02 46.05 58.04 67.82 76.17 83.53 90.13 96.15 101.70 106.87 111.71 116.27 120.59 124.71 128.63 132.40 136.0-

11

139.49 142.85 146.10

R134a

[

°

C]

-26.43 -4.29

8.93

18.75 26.72 33.49 39.43 44.75 49.58 54.02 58.14 61.99 65.62 69.04 72.30 75.40 78.36 81.20 83.93 86.57 89.11

R142B

[

°

C]

-10.07 15.44 30.54 41.71 50.72 58.37 65.05 71.01 76.42 81.38 85.98 90.27 94.29 98.09 101.70 105.13 108.40 111.54 114.55 117.44 120.24

R227

[

°

C]

-17.58

5.82

20.05 30.76 39.52 47.03 53.66 59.63 65.09 70.13 74.83 79.24 83.41 87.37 91.13 94.74 98.20 101.52 104.73 107.83 110.83

R401

[

°

C]

-27.05 -4.65

8.71

18.63 26.68 33.52 39.52 44.89 49.77 54.25 58.41 62.30 65.96 69.41 72.70 75.82 78.81 81.68 84.44 87.09 89.66

R401A

[

°

C]

-29.21 -6.93

6.40

16.33 24.39 31.26 37.28 42.68 47.59 52.10 56.29 60.22 63.91 67.40 70.72 73.88 76.91 79.81 82.60 85.29 87.99

R401B

[

°

C]

-28.97 -6.74

6.52

16.37 24.35 31.14 37.08 42.41 47.24 51.69 55.81 59.67 63.29 66.72 69.97 73.07 76.03 78.87 81.60 84.23 86.77

R402

[

°

C]

-47.59 -26.34 -13.71 -4.36

3.21

9.64

15.26 20.29 24.85 29.04 32.92 36.55 39.95 43.17 46.23 49.13 51.91 54.57 57.13 59.59 61.97

R402A

[

°

C]

-47.59 -26.34 -13.71 -4.36

3.21

9.64

15.26 20.29 24.85 29.04 32.92 36.55 39.95 43.17 46.23 49.13 51.91 54.57 57.13 59.59 61.97

R402B

[

°

C]

-45.46 -24.06 -11.33 -1.89

5.75

12.23 17.92 22.99 27.61 31.84 35.77 39.44 42.89 46.14 49.23 52.18 54.99 57.69 60.28 62.77 65.18

R404A

[

°

C]

-46.36 -24.92 -12.18 -2.74

4.89

11.37 17.04 22.11 26.72 30.94 34.86 38.52 41.95 45.20 48.28 51.21 54.01 56.70 59.28 61.67 64.16

R407A

[

°

C]

-39.47 -18.64 -6.32

2.78

10.13 16.36 21.80 26.66 31.06 35.10 38.84 42.33 45.60 48.69 51.62 54.41 57.07 59.62 62.06 64.42 66.69

R407B

[

°

C]

-43.49 -22.74 -10.44 -1.34

6.01

12.24 17.69 22.55 26.97 31.02 34.77 38.27 41.56 44.66 47.61 50.41 53.09 55.65 58.11 60.48 62.76

R407C

[

°

C]

-37.31 -16.35 -3.95

5.22

12.62 18.89 24.37 29.27 33.70 37.77 41.54 45.06 48.36 51.47 54.43 57.24 59.92 62.49 64.96 67.34 69.63

R500

[

°

C]

-33.80 -10.77

3.02

13.28 21.62 28.72 34.96 40.54 45.62 50.29 54.63 58.69 65.51 66.13 66.56 72.83 75.97 78.97 81.86 84.65 87.34

R502

[

°

C]

-45.54 -23.63 -10.53 -0.77

7.15

13.89 19.81 25.10 29.92 34.35 38.47 42.32 45.94 49.37 52.62 55.72 58.69 61.54 64.28 66.91 69.46

R503

[

°

C]

-88.64 -70.55 -59.77 -51.77 -45.29 -39.79 -34.96 -30.65 -26.73 -23.12 -19.78 -16.66 -13.72 -10.95 -8.32

-5.81

-3.41

-1.11

1.10

3.22

5.28

R507

[

°

C]

-46.51 -25.59 -13.02 -3.64

3.98

10.49 16.20 21.32 25.99 30.28 34.28 38.01 41.53 44.86 48.03 51.05 53.94 56.72 59.39 61.97 64.46

R717

[

°

C]

-33.59 -13.65 -1.88

6.80

13.80 19.73 24.91 29.52 33.71 37.54 41.09 44.40 47.50 50.43 53.21 55.84 58.36 60.78 63.09 65.32 67.46

Operating Instructions

Acontrol

model series PKE-6 /-10 / PKE-14

Setting for operation

L-BAL-E042-GB 1002 Index002

Part.-No. 00163314-GB

19/26

Содержание Acontrol PKE-6

Страница 1: ...ntrol PKE 6 10 PKE 14 P controller and speed controller for variable voltage 1 fans Operating Instructions Software version D1361A from Version 00 L BAL E042 GB 1002 Index 002 Part No 00163314 GB engl...

Страница 2: ...uences during commissioning 7 5 Electrical installation 8 5 1 Safety precautions 8 5 2 EMC compatible installation 8 5 2 1 Motor feeder cable 8 5 2 2 Signal cable 8 5 3 Mains connection 8 5 4 Motor co...

Страница 3: ...mperature control Heating function 17 9 3 Pressure control condensers P Controller 3 01 18 9 3 1 Setting for operation as Pressure controller 18 9 3 2 Example Pressure control condensers 18 9 3 3 Sett...

Страница 4: ...illustrations or drawings provided Ziehl Abegg AG is not liable for damage due to misuse incorrect use improper use or as a consequence of unauthorized repairs or modi cations 1 4 Copyright These oper...

Страница 5: ...Also note the instructions of AEL DLG VdS 2 4 Requirements placed on the personnel due diligence Persons entrusted with the planning installation commissioning and maintenance and servicing in connec...

Страница 6: ...tractor or owner must also ensure that the electric systems and equipment are operated and maintained in accordance with electro technical regulations The owner is obliged to ensure that the device ar...

Страница 7: ...e on a clean and stable base Do not distort during assembly Use the appropriate mounting devices for proper installation of the unit Do not mount equipment on vibrating base When mounted onto lightwei...

Страница 8: ...arance or thermal shielding is required 4 3 Outdoor installation Outdoor installation is possible up to 20 C when the controller supply is not switched off Installation must be protected from the effe...

Страница 9: ...astic housing parts because there is no potential equalization Never clean electrical equipment with water or similar liquids Information The respective connections are represented in the enclosure of...

Страница 10: ...ection is required We cannot under any circumstances accept liability for damage to the motors which do not have the required motor protection It is recommended that every fan is equipped with a separ...

Страница 11: ...ted Attention No disconnection isolation when turned off in accordance with VBG4 6 Never apply line voltage to the digital input It is not permissible to connect inputs of several devices to each othe...

Страница 12: ...over n max Potentiometer n max Pband Function dependently on selected mode of operation For speed controller 1 01 Maximal output voltage speed limiter Setting range 100 n min 100 output voltage fully...

Страница 13: ...tches Attention Setting of jumper and switches not under voltage Observe the safety notices Changed functions become active partly only after renewed switching on the mains voltage E1 Analog In factor...

Страница 14: ...tch S1 Position factory setting for all dipswitches OFF DIP Function OFF ON 1 Selection Speed controller P Controller Speed controller P Controller 2 Minimum speed cut off OFF ON 3 Type of Signal 0 10...

Страница 15: ...ON OFF approx 2 5 of 100 set value nM 50 100 I Min Min 35 Max 100 20 C S 7 K R 27 C 2 0 K 10 05 2007 v_min_luft_abschalt vsd Minimum speed cut off idealized principle diagram nM Motor speed S Setpoin...

Страница 16: ...priority if over n max 28 08 2008 v_nmax_pband_pke VSD n max P band R 4 9 5 30 n max Pband Maximal output voltage speed limiter Setting range 100 n min 100 output voltage fully clockwise position 30 9...

Страница 17: ...mperature control with passive sensors TF KTY Setting range 0 100 26 76 C measuring range of controller Scale 0 100 26 76 C for Temperature control with passive sensors TF KTY set 0 5 10 15 20 25 30 3...

Страница 18: ...C n min 35 Idealized principle diagram 9 2 3 Example Temperature control Heating function Val Set n DIP4 ON Temperature sensor type TF Measuring range controller 26 76 C Settings set 50 25 C 102 K 10...

Страница 19: ...0 100 5 30 measuring range of sensor 0 100 n min R 4 8 28 08 2008 v_nmin_pke VSD n min Minimum output voltage basic speed Setting range 0 100 n min takes priority if over n max 9 3 2 Example Pressure...

Страница 20: ...5 58 41 62 30 65 96 69 41 72 70 75 82 78 81 81 68 84 44 87 09 89 66 R401A C 29 21 6 93 6 40 16 33 24 39 31 26 37 28 42 68 47 59 52 10 56 29 60 22 63 91 67 40 70 72 73 88 76 91 79 81 82 60 85 29 87 99...

Страница 21: ...r max imum signal values depending on selected signal type The device works with minimal or maximum modula tion depending on whether there is a short circuit or an interruption and on the programmed m...

Страница 22: ...densation Electromagnetic compatibility for the standard voltage 230 400 V according to DIN IEC 60038 Interference emission EN 61000 6 3 domestic household applications Interference immunity EN 61000...

Страница 23: ...KTY 4 1 E1 V mA C GND 24 V M 1 PE U1 U2 1 Motor ohne Thermostatschalter without thermostats 2 1 Line 1 230 V 50 60 Hz 2 1 Motor without thermostats 3 Output 0 10 V Imax 10 mA 4 Input 0 10 V 2 10 V 0...

Страница 24: ...reglerad spanning 1 60V 250V 50 60Hz 1 2 4 6 12 11 24 23 Option ZB ZK 2S Kontaktbelastung der Hilfskontakte contact rating of auxiliary contacts pouvoir de coupure des contacts auxiliaires Kontaktbel...

Страница 25: ...del series PKE 6 10 PKE 14 Enclosure L BAL E042 GB 1002 Index 002 Part No 00163314 GB 24 26 11 3 Dimensions mm PKE 6 PKE 10 PKE 14 Switch off the main supply before removing the cover Vor ffnen des De...

Страница 26: ...tance 21 L line fuse 21 M mains is connected 8 mains voltage 8 maximum control current 9 MBG 30I 18 Minimum space requirement 7 Minimum speed cut off 14 Mode 12 motor feed cable 8 motor noise 9 motor...

Страница 27: ...e information If you have any technical questions while commissioning or regarding malfunctions please contact our V STE support department for control systems ventilation technology Our worldwide con...

Отзывы: