9 Setting for operation
9.1
Speed controller
1.01
9.1.1
Setting for operation as Speed controller
Signal to:
E1
E1
GND
14.02.2008
v_signal_e1.vsd
E1
Setting via external signal or external potentiometer
Setting range: Output voltage from approx. 0 - 100 % of connected line
voltage or in range of settings
“
n-min
”
up to
“
n-max
”
.
(Potentiometer
set
without function)
%
0
100
n-min
R
4
8
28.08.2008
v_nmin_pke.VSD
n-min
Setting of output voltage at the device 0 - 100 %.
For setting via external signal: Minimum output voltage (basic speed)
Setting range: 0 - 100 % (
“
n-min
”
takes priority if over
“
n-max
”
).
28.08.2008
v_nmax_pband_pke.VSD
n-max /
P-band
R
4
9
%
5
30
n-max / Pband
Maximal output voltage (speed limiter)
Setting range: 100 % -
“
n-min
”
(100 % output voltage = fully clockwise position 30 %)
9.1.2
Diagram: setting signal and speed
nM
50 %
100 %
0
1
2
3
4
5
6
7
8
9
10
10
9
8
7
6
5
4
3
2
1
0
0
2
4
6
8
10
12
14
16
18
20
20
18
16
14
12
10
8
6
4
2
0
4
5,6
7,2
8,8
10,4
12
13,6 15,2 16,8 18,4
20
20
18,4 16,8 15,2 13,6
12
10,4
8,8
7,2
5,6
4
0 – 10 V
10 – 0 V
0 – 20 mA
20 – 0 mA
4 – 20 mA
20 – 4 mA
Min.
Min. 0 %
Max. = 100 %
Min. 35 %
Max. = 85 %
05.02.2008
v_nmotor_101_miluab.vsd
Si
Idealized principle diagram
nM Motor speed
Si Signal
Operating Instructions
Acontrol
–
model series PKE-6 /-10 / PKE-14
Setting for operation
L-BAL-E042-GB 1002 Index002
Part.-No. 00163314-GB
15/26