background image

Montageanleitung

Drehstrom-Asynchronmotoren 
nach DIN EN 50347

gemä

ß

 Niederspannungsrichtlinie 2014/35/EU 

Inhalts

ü

bersicht

Kapitel

Seite

Allgemein. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Bestimmungsgemä

ß

e Verwendung . . . . . . . . . . . . . . 1

Transport, Lagerung . . . . . . . . . . . . . . . . . . . . . . . . 2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Elektrischer Anschluss. . . . . . . . . . . . . . . . . . . . . . . 3
EMV-gerechte Installation. . . . . . . . . . . . . . . . . . . . . 3
Inbetriebnahme. . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Entsorgung / Recycling . . . . . . . . . . . . . . . . . . . . . . 5
Hersteller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Serviceadresse. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Die Einhaltung der nachfolgenden Vorgaben dient auch der 
Sicherheit des Produktes. Sollten die angegebenen Hinweise 
insbesondere zur generellen Sicherheit, Transport, Lagerung, 
Montage, Betriebsbedingungen, Inbetriebnahme, Instandhal-
tung, Wartung, Reinigung und Entsorgung / Recycling nicht 
beachtet werden, kann das Produkt eventuell nicht sicher 
betrieben werden und kann eine Gefahr f

ü

r Leib und Leben der 

Benutzer und dritter Personen darstellen. 
Abweichungen von den nachfolgenden Vorgaben können 
daher sowohl zum Verlust der gesetzlichen Sachmängelhaf-
tungsrechte f

ü

hren als auch zu einer Haftung des Käufers f

ü

das durch die Abweichung von den Vorgaben unsicher gewor-
dene Produkt.

Allgemein

Niederspannungsmaschinen haben gefährliche, span-
nungsf

ü

hrende und rotierende Teile sowie möglicherweise

hei

ß

e Ober

ächen. Alle Arbeiten zum Transport, Anschluss,

zur Inbetriebnahme und Instandhaltung sind von quali

-

ziertem, verantwortlichem Fachpersonal auszuf

ü

hren (EN

50110-1 / VDE 0105; IEC 364 beachten). Unsachgemä

ß

es

Verhalten kann schwere Personen- und Sachschäden
verursachen.

Bestimmungsgemä

ß

e Verwendung

Diese Niederspannungsmaschinen sind f

ü

r gewerbliche

Anlagen bestimmt. Sie entsprechen den harmonisierten
Normen der Reihe EN 60034 (VDE 0530). Der Einsatz im
Ex-Bereich ist verboten, sofern nicht ausdr

ü

cklich hierf

ü

r

vorgesehen (Zusatzhinweise beachten).

Schutzarten 

 IP 23 keinesfalls im Freien verwenden.

Luftgek

ü

hlte Ausf

ü

hrungen sind f

ü

r Umgebungstempera-

turen von 0

°

C bis +40

°

C f

ü

r Motoren mit einer Leistung 

600W bzw. -20

°

C bis 40

°

C f

ü

r Motoren mit einer Leistung >

Assembly instructions

Three-phase current induction 
motors acc DIN EN 50347

in conformity with the low-voltage directive 2014/35/EU

Contents

Chapter

Page

General information. . . . . . . . . . . . . . . . . . . . . . . . . 1
Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Transport, storage . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . 3
EMC-compatible installation . . . . . . . . . . . . . . . . . . . 3
Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Disposal / recycling . . . . . . . . . . . . . . . . . . . . . . . . . 5
Manufacturer: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Service address . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Compliance with the following instructions is mandatory to 
ensure the functionality and safety of the product. If the 
following instructions given especially but not limited for 
general safety, transport, storage, mounting, operating condi-
tions, start-up, maintenance, repair, cleaning and disposal / 
recycling are not observed, the product may not operate safely 
and may cause a hazard to the life and limb of users and third 
parties. 
Deviations from the following requirements may therefore lead 
both to the loss of the statutory material defect liability rights 
and to the liability of the buyer for the product that has become 
unsafe due to the deviation from the speci

cations. 

General information

Low-voltage machines have dangerous live and rotating
parts and possibly hol surfaces. All operations serving trans-
port, connetion, com-missioning and maintenance are tobe
carried out by skilled, responsible technical personnel (in
conformity with EN 50110-1 /VDE 0105; IEC 364). Improper
handling may cause serious personal injury and damage to
property.

Intended use

These low-voltage machines are intended for industrial and
commercial installations. They comply with the harmonized
series of standards EN 60034 (VDE 0530). Their use in
hazardous areas is prohibited unless they are expressly
intended for such use (follow additional instructions).

The degrees of protection 

 IP 23 are by no means intended

for outdoor use.

Air-cooled models are rated for ambient temperatures of
0

°

C to +40

°

C for motors with a power of 

 600W or -20

°

C to

40

°

C for motors with a power of > 600W and altitudes of 

1

english

deutsch

002881

12

L-BAL-029-GB-2718-Index 

00

9

Содержание 50347

Страница 1: ...ren nach DIN EN 50347 Three phase current induction motors acc DIN EN 50347 gemäß Niederspannungsrichtlinie 2014 35 EU in conformity with the low voltage directive 2014 35 EU Montageanleitung Assembly instructions Für künftige Verwendung aufbewahren Keep for future use ...

Страница 2: ...eistung 600W bzw 20 C bis 40 C für Motoren mit einer Leistung Assembly instructions Three phase current induction motors acc DIN EN 50347 in conformity with the low voltage directive 2014 35 EU Contents Chapter Page General information 1 Intended use 1 Transport storage 2 Installation 2 Electrical connection 3 EMC compatible installation 3 Start up 4 Disposal recycling 5 Manufacturer 5 Service add...

Страница 3: ...t Die Belüftung darf nicht behin dert und die Abluft auch benachbarter Aggregate nicht unmittelbar wieder angesaugt werden d Durchmesser der Lufteintrittsöffnung 1000 m above sea level Stricty observe different instruc tions an the rating plate Conditions an site must conform to all rating plate markings The safety guidelines in the Low Voltage Directive 2014 35 EU are complied with only if proper...

Страница 4: ... Gegenring zu verwenden Electrical connection All operations may be carried out only by skilled technical personnel an the Iow voltage machine at rest and de ener gized and provided wich a safeguard to prevent uninten tional reciosing This also applies to auxiliary circuits e g thermal motor protection check safe isolation from supply Torque for screw connections in the electrical connections Term...

Страница 5: ...felsfall Niederspannungs maschine abschalten Bei starkem Schmutzanfall Luftwege regelmäßig reinigen Lagerungen mit Nachschmiereinrichtungen bei laufender Niederspannungsmaschine nachfetten Verseifungsart beachten Falls Fettaustrittsbohrungen mit Stopfen verschlossen sind IP55 auf Abtriebsseite IP23 auf Reducing bearing currents when operating on the inverter When operating on the inverter harmful ...

Страница 6: ...om output side IP23 on output and non driving side remove plugs before putting into operation Close holes with grease Bearing replacement in case of permanent lubrication 2 Z bearing after ca 20 000 hrs for 2 to 12 pole low voltage machines but in any case latest after 3 4 years or in accord ance with the manufacturer s specifications Disposal recycling Disposal must be carried out professionally a...