Repairs of electrical parts and refrigeraion circuit 

Trouble shooting

only by qualified technician

Malfunction

Cause

Remedial Action

Highpressure switch

Air in refrigeration circuit

evacuate circuit, refill refrigerant

has switched off

(insufficiently evacuated after repair)

o  

Control lamp shows red

Refrigeration circuit overfilled

adjust

air-cooled machine:

machine must not be placed in the sun or

*

ambient temperature too high

 too warm ambience. Improve ventilation.

*

condenser soiled

clean with brush or compressed air, 
never with wire brush

*

ventilator motor or speed control

check / replace

defective

water-cooled machine:

*

insufficient water pressure

increase water pressure to min 2 bar

*

condenser soiled

clean condenser with bottle brush,
hot water and antilime agent
clean water filter

*

water or condensing pressure

check / clean / replace

governor misadjusted, soiled
or defective

Cut - out  by compressor

*

compressor overheated

depending on ambient temperature let
machine cool for 3 hours, compressor 
starts again automatically

*

wrong electrical connection

check

or defective protection switch

*

compressor defective

check / replace

Light barrier does not work

*

transmitter and receiver not in line

adjust

*

defective

check manually at short distance

*

dirty or lime scale

clean

Ice jam switch has cut off

switch defective

check

Ice jams back into cylinder

eliminate cause, readjust ice hose and
security switch. (page 3 point 13)

6

Содержание UBE 1.500

Страница 1: ...e quality Miscellaneous 7 Cleaning of freezing unit 8 Wiring diagram attached Cooling circuit General installation advice Assembly Instruction Freezing Unit Spare parts list Subject to technical modif...

Страница 2: ...tating auger does not form part of the refrigeration circuit Therefore leakages in the refrigeration system caused by rotating parts cannot occur The ideal ice temperature is 0 5 C ZIEGRA Chip ice has...

Страница 3: ...the machine Tighten all electrical connections in the control and at water temperatures above 15 C resp 25 C panel as they may have loosened during the production capacity may decrease transport Cran...

Страница 4: ...s full This light barrier has been chosen by us for these 10 Phase sequence Relay particular conditions Please contact us The phase sequence relay switches off the machine if the phases are not connec...

Страница 5: ...if necessary V belts check replace if necessary A loose V belt does not transfers the load correctly on the auger This will overload the freezing unit Ice hose and water retainer calcified clean or re...

Страница 6: ...eck connection and fuses Fuses blow up Check Intermittent contact Check electrical connections also in control panel Water pressurestat or readjust or replace Water level control defective readjust or...

Страница 7: ...cooled machine insufficient water pressure increase water pressure to min 2 bar condenser soiled clean condenser with bottle brush hot water and antilime agent clean water filter water or condensing p...

Страница 8: ...ust evaporation temperature as indicated Check thermal feeler pipe and contact at evaporator outlet insufficient amount of refrigerant remove leak evacuate circuit refill bubbles in sight glass with i...

Страница 9: ...unit into a container o Connect a hose of appr 80 cm with funnel at the water inlet of the freezing unit o Mix cleaning agent with hot water For each freezing unit 1 2 bottle agent in 1 litre water o...

Отзывы: