-75-
F-1 DISPLAY
Explanation 1
The Flame check at initial burning (Initial condition) – T8 implies a time span of 2 minutes and thirty
seconds from the end of preheating (approximately 40 to 150 sec. – SRE 156, 166, 176, 710, 810;
approximately 40 to 180 sec. – SRE 186; approximately 60 to 80 sec. – SRE 260). After ignition is made,
a forced Med.-burning of 40 seconds will be followed.
Preheating Time
(40-150 sec. - SRE 156,166,176,710,810)
Flame check at initial burning (Initial condition) – T8
(40-210sec. – SRE 186)
(150 sec.)
F-1
(60-180sec. – SRE 260)
Power
Blower
Pump
Button On
On
On
40 sec.
Forced Med.-Burning
Explanation 2
The Igniter is red-heated in approximately 30 seconds
after pressing the Power Button. If this does not occur,
check by tester to see if the resistance of the Igniter is
proper. If the Igniter does not show a resistance of 40 to
49
Ω
, change it with the new Igniter. If the Igniter is not
abnormal, the Main Circuit Board is assumed to be
defective. Check by measuring the output voltage on the
side of Main Circuit Board, which voltage must be AC
230V.
Explanation 3
If the resistance of the Burner Thermistor is more than 950
k
Ω
after Forced Burning timing and yellow or white colored flames are
at more than 900 k
Ω
(or if the Burner Thermistor temperature is lower
than approximately 160 °C), “F-1” will be displayed to stop the
operation. If the Burner Thermistor is broken or the terminal is not
connected, this safety device is actuated.
Resistances of the Burner Thermistor:
Thermistor Temperature
SRE 156
SRE 166
(Yellow)
SRE 176
SRE 250
SRE 260
(Orange)
Approx. 20 °C
Approx. 20 M
Ω
Approx. 120 M
Ω
Approx. 250 °C
Approx. 8 k
Ω
Approx. 58 k
Ω
Approx. 300 °C
Approx. 3.34 k
Ω
Approx. 25 k
Ω
To be replaced, if not within
40-49
Ω
at a room temp. of
23 °C.
Igniter is disconnected.
Igniter with resistance failure.
Explanation 2
Displayed
after
preheating
time.
Displayed
when
finishing
Forced
Burning
timing.
Explanation 1
Defective Main Circuit
Board
Igniter is not red-heated.
Part replacement.
Burner
thermistor
is
disconnected or terminal is
out of engagement.
Explanation 3
Lack
of
Burner
preheat.
Replacement or correction of
Burner Thermistor.
F-1 is displayed and
the
Heater
is
extinguished.