“PV” collect data
AL-1 NC terminal
AL-1 NO terminal
AL-1 indicator
More than 5.20
open
close
light
Between 4.8 and 5.2
maintain the previous state
Less than 4.8
close
open
dark
Example 2 :
if setting the AL-1 as
“5.00 “ , setting the SEL1 as “LJ” , setting the HC-1 as “ 0.20 “ .
In working state, AL-1 relay working status as following :
“PV” collect data
AL-1 NC terminal
AL-1 NO terminal
AL-1 indicator
More than 5.20
close
open
dark
Between 4.8 and 5.2
maintain the previous state
Less than 4.8
open
close
light
4.21 ) the second pressure alarm function settings (SEL2)
In working state, press the "SET" once ,
” PV” shows “ SV ” , then loosen the button .
Press
“ SET “ again for 5 seconds , it will enter into output amplitude high limited value setting , “ PV
“ shows “ OL-U “, then loosen the button .
Then Press
“ SET “ seven times , enter into the second pressure alarm function settings ,” PV “ shows
“ SEL2” .
Pressure "
∧
" or "
∨
" to shift the second pressure alarm function (HJ or LJ ) status .
Setup completed, press "MODE" button to return to work, or press the "SET" button enter into the scond
pressure alarm hysteresis zone setting .
4.22 ) the second pressure alarm hysteresis zone setting .( HC-2)
In working state, press the "SET" once ,
” PV” shows “ SV ” , then loosen the button .
Press
“ SET “ again for 5 seconds , it will enter into output amplitude high limited value setting , “ PV
“ shows “ OL-U “, then loosen the button .
Then Press
“ SET “ eight times , enter into the second pressure alarm hysteresis zone setting , “ PV
“ shows “ HC-2 “ .
Press "<" to adjust "SV" Numbers flashing, flashing a is modified;
press "
∧
" or "
∨
" adjust the flashing value up to down ;
Setup completed, press "MODE" button to return to work, or press the "SET" button enter into the pressure
division value settings .
The functional role:
the AL-2 is similar as AL-1 , but AL-2 no NC terminal , we just supply the NO terminal .
4.23 ) the pressure division value settings
In working state, press the "SET" once ,
” PV” shows “ SV ” , then loosen the button .
Press
“ SET “ again for 5 seconds , it will enter into output amplitude high limited value setting , “ PV
“ shows “ OL-U “, then loosen the button .
Then Press
“ SET “ nine times , enter into the pressure division value settings . “ PV “ shows “ DP “ .