4.15) Output amplitude low limited value settings 

In working state, press the "SET" once ,

” PV” shows “ SV ” , then loosen the button 

Press 

“  SET  “  again  for  5  seconds  ,  it  will  enter  into  output  amplitude  high  limited  value  setting  ,  “  PV 

“ shows “ OL-U “, then loosen the button . 
Press 

“ SET “ once again , enter into output amplitude low limited value settings , “ PV “ shows “ OL-L “. 

Press "<" to adjust "SV" Numbers flashing, flashing a is modified; 

press    "

" or "

" adjust the flashing value up to down ; 

Setup completed, press "MODE" button to return to work, or press the "SET" button enter into Transducer 

pressure range value settings . 

 

For example :

 if the controller output is 0-10v , Output amplitude high limited value setting 

“ 10.0”    ; then 

the  controller  output  maximum  value  will  be  1V  ,  no  matter  manual  or  automatic  adjust  ,  the  controller 

output value is not less than 1V . 

In the manual control , is not subject to this value, the lowest drops to zero. 

 

The functional role:

 to prevent discharging stuck, instantaneous pressure caused by the phenomenon of 

downtime. The exact value setting , need users according to the actual usage Settings. 

 

4.16 ) Transducer pressure range value settings . 

Instrument range should be match with the instrument range setting value , then it will display the properly 

pressure value . so firstly check the transducer range, if such ranges does not match, follow these steps. 

In working state, press the "SET" once ,

” PV” shows “ SV ” , then loosen the button . 

Press 

“  SET  “  again  for  5  seconds  ,  it  will  enter  into  output  amplitude  high  limited  value  setting  ,  “  PV 

“ shows “ OL-U “, then loosen the button . 
Then Press 

“ SET “ twice , enter into transducer pressure range value settings    , “ PV “ shows “ ED “. 

Press "<" to adjust "SV" Numbers flashing, flashing a is modified; 

press    "

" or "

" adjust the flashing value up to down ; 

Setup  completed,  press  "MODE"  button  to  return  to  work,  or  press  the  "SET"  button  enter  into  Decimal 

point location settings . 

 

For example :

 if the controller current range is   

“ 10.00 “    , and transducer pressure range is 15MPa , 

according to the above steps, and setting the controller range to "15.00". 

 

4.17) The decimal point location settings 

In working state, press the "SET" once ,

” PV” shows “ SV ” , then loosen the button . 

Press 

“  SET  “  again  for  5  seconds  ,  it  will  enter  into  output  amplitude  high  limited  value  setting  ,  “  PV 

“ shows “ OL-U “, then loosen the button . 
Then Press 

“ SET “ three times , enter into decimal point location settings , “ PV “ shows “ DOT “. 

Press "<" to adjust the decimal point location ; 

Setup completed, press "MODE" button to return to work, or press the "SET" button enter zero/ span value 

settings . 

 

 

Содержание PD9001

Страница 1: ...Shanghai Zhaohui Pressure Apparatus Co Ltd www zhyqsensor com info zhyqsensor com Tel 86 21 51691919 Fax 86 21 67755185 ZHYQ Digital Controller Operation Manual PD9001...

Страница 2: ...lity and reliability of the system The instrument technical indicators are as follows Digital Display Double layer double color four digital display green and red Electronic bar display 20 segments el...

Страница 3: ...key m SET Function key the pressure value would be zero clearing if you press thefunction key and AC reset key at the same time n Shift key if you mistake the zero clearing operation now you need to...

Страница 4: ...hielded shielded 14 220V power supply input L 7 PID output PID output 15 220V power supply input N 8 PID output PID output 16 Ground 2 4 2 transducer input 4 20mA 0 5V 0 10V terminal Function transduc...

Страница 5: ...ure range 1 9999 According to the transducer full range 1000 DOT Decimal point location selection 0000 000 1 00 01 0 0001 dddd no decimal ddd d 1 decimal dd dd 2 decimal d ddd 3 decimal 00 01 ESCL Zer...

Страница 6: ...ctual output value for example if output type 4 20 mA SV shows a value of 80 0 the actual output value of 16 8 mA Press reduce output Press increase the output 4 3 Sampling data reset make sure connec...

Страница 7: ...djust the flashing value up to down After enter the password press SET to validate initial password 0000 Password authentication is passed enter into new password Settings PV shows NPAS Press the adju...

Страница 8: ...enter into AL 2 parameter Settings 4 13 The second pressure alarm AL 2 value settings In working state press the SET six times PV shows AL 2 Press to adjust SV Numbers flashing flashing a is modified...

Страница 9: ...sducer pressure range value settings Instrument range should be match with the instrument range setting value then it will display the properly pressure value so firstly check the transducer range if...

Страница 10: ...the SET once PV shows SV then loosen the button Press SET again for 5 seconds it will enter into output amplitude high limited value setting PV shows OL U then loosen the button Then Press SET five t...

Страница 11: ...essure alarm function HJ or LJ status Setup completed press MODE button to return to work or press the SET button enter into the scond pressure alarm hysteresis zone setting 4 22 the second pressure a...

Страница 12: ...high limited value setting PV shows OL U then loosen the button Then Press SET eleven times enter into the output adjustment cycle settings PV shows TS press or to adjust SV value Setup completed pres...

Страница 13: ...el Range bar Input Output Power Supply Alarm Other requirement PD9001 Example PD9001 350BAR 4 20mA 0 10V 220V 2 7 ZHYQ contacts Company Name Shanghai Zhaohui Pressure Apparatus Co Ltd Address 5 6F No...

Отзывы: